Omron W343-E1-07 User Manual

Page 119

Advertising
background image

98

Sending Commands From a Host Computer

Section 5-4

FINS Command Frame Configuration

FINS Response Frame
Configuration

The response code (one byte each for MRES and SRES) for the command is
added at the beginning of the FINS parameter/data field in the response
frame.

FINS Header Information

ICF (Information Control Field)

RSV (Reserved by system)

Set to 00 (Hex).

GCT (Permissible Number of Gateways)

Set to 02 (Hex).

DNA (Destination Network Address)

Specifies the number of the network where the destination node is located.
00 (Hex):

Local network

01 to 7F (Hex): Destination network number (1 to 127)

DA1 (Destination Node Address)

Specifies the number of the node where the command is being sent. This
node number is the address used for FINS, and is different from the IP ad-

FINS header

FINS command

FINS parameter/data

Parameter/
data field

Size (bytes)

Contents

Displays frame information

Reserved by system.

Permissible number of gateways

Destination network address

Destination node address
Destination unit address

Source network address

Source node address

Source unit address

Service ID

Main request code

Sub-request code

2000 max.

Command parameters and send data

The data length depends on the MRC and SRC.

1

1

1

1

1

1

1

1

1

1

1

1

ICF

RSV

GCT

DNA

DA1

DA2

SNA

SA1

SA2

SID

MRC

SRC

FINS
parameter/data field

FINS header

FINS command

Data

Size (bytes)

Contents

Same as in command frame.

Same as in command frame.

Main response code

Sub-response code

1998 max.

Response data

There are some frames in which
the data length is 0.

10

2

1

1

MRES

SRES

7

6

5

4

3

2

1

0

1 0 0 0 0 0

Bit

Response Request Bit
(0: Response required; 1: Response not required)
Kind of data (0: command; 1: response)

Advertising