Omron ETHERNET DIRECT DR 170 14 User Manual

Page 42

Advertising
background image

Klinkmann Automation Omron Ethernet DAServer

40


Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4 17014m14

C200HX/C200HG/C200HE PLCs

The following table lists the supported item names for the C200HX, C200HG and
C200HE PLCs.

Memory Area

Prefix

Tag

Type

Address Range

Value

Range

Suffix

Internal Relay Area 1, 2
Special Relay Area 1, 2

(Bit status)

IR

Discrete IR0:00...IR511:15

or

0.00...511.15

0, 1

Internal Relay Area 1, 2

Special Relay Area 1, 2

(Word contents)

IR

Integer

IR0... IR511

or

0…511

(*)

u s b f g l

m d e c

Link Relay Area

(Bit status)

LR

Discrete

LR0:00...LR63:15

0, 1

Link Relay Area

(Word contents)

LR

Integer

LR0... LR63

(*)

Holding Relay Area

(Bit status)

HR

Discrete HR0:00... HR99:15

0, 1

Holding Relay Area

(Word contents)

HR

Integer

HR0... HR99

(*)

u s b f g l

m d e c

Auxiliary Relay Area

(Bit status)

AR

Discrete AR0:00... AR27:15

0, 1

Auxiliary Relay Area

(Word contents)

AR

Integer

AR0... AR27

(*)

u s b f g l

m d e c

Timer/Counter Area

Completion Flag(****)

TC

Discrete

TC0... TC511

0, 1

Timer/Counter Area

(PV)

PV

Integer

PV0... PV511

(*)

u s b f g l

m d e c

Data Memory Area

(Bit status)(**)

DM

Discrete

DM0:00...

DM9999:15

0, 1

Data Memory Area

(Word contents)(**)

DM

Integer

DM0...

DM9999

(*)

u s b f g l

m d e c

Extended Data Memory

Area (Bit status)(***)

EM

Discrete

EM0:00...

EM6143:15

0, 1

Extended Data Memory

Area Word contents(***)

EM

Integer

EM0... EM6143

(*)

u s b f g l

m d e c


Item/point names, corresponding to Internal Relay/Special Relay Area may be without
prefix.

(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default
value range for Integer Tag Type is unsigned integer.
(**) Memory area range DM7000…DM9999 is supported only if Expansion DM Area is
allocated on the PLC.
(***) Current bank only (Memory Area code 98).