Klinkmann Automation Omron Ethernet DAServer

48


Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4 17014m14

DAServer Global System Item

The following system item refers to specific information regarding a global condition of the
DAServer.

System Item

Name

Type/

Access

Rights

Description

Values

$SYS$Licensed Boolean/

Read

Binary status indication of the
existence of a valid license for the
DAServer.
If FALSE, this item causes the
DAServer to stop updating existing
tags, to refuse activation of new tags,
and to reject write requests in addition
to setting quality for all items to BAD.
If TRUE, the DAServer functions as
configured.
All instances have the same value.

RANGE: 0, 1

1: Valid license
exists.

0: No valid
license exists.


Note: With Omron Ethernet DAServer Global System Item $SYS$Licensed is not
relevant.

DAServer Device-Specific System Items

The following system items refer to specific information regarding the device(s) the
DAServer is connected to.

System Item

Name

Type/

Access

Rights

Description

Values

$SYS$Status

Boolean/
Read

Binary status indication of the
connection state to the device
(hierarchy level) the item is
attached to.
The device group (OPC access
path/topic) does not affect the
value. The status can be good
even if individual items have
errors.
For DDE/SuiteLink clients,
$SYS$Status always comes
from the leaf level of a DAServer
hierarchy branch, which is the
destination PLC node.
For OPC clients, $SYS$Status
can be accessed at all hierarchy
levels. $SYS$Status at the root
level of the whole hierarchy tree
is always good, as it represents
the quality status of the local
computer itself. Hence, for

RANGE: 0, 1

1: DAServer
connection to the
device is intact.
0: Error
communicating
with the device.