Omron ETHERNET DIRECT DR 170 14 User Manual

Page 64

Advertising
background image

Klinkmann Automation Omron Ethernet DAServer

62


Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4 17014m14

operation manual)

04

Node number setting
error.

Make sure the node
number is within
specified range and that
there are no duplicate
node numbers.

DASProtFail

04: Not
executable

01

An undefined
command has been
used, or short frame (4
bytes) is being used for
FINS header frame.

Check the command
code and be sure code
is supported by Unit to
which command is
sent.(*)

DASProtFail

05: Routing
error

01

Destination node
number is not set in the
routing tables.

Set the remote PLC in
the routing tables.

DASProtFail

02

Routing tables aren't
registered.

Set the the routing
tables at the relay nodes
and remote node.

DASProtFail

03

Routing table error.

Set the the routing
tables correctly.

DASProtFail

04

The maximum number
of relay nodes (2) was
exceeded in the
command.

Redesign the network to
reduce number of relay
nodes.

DASProtFail

10:
Command
format error

01

The command is longer
than the max.
permissible length.

Check the command
format and set it
correctly.(*)

DASProtFail

02

The command is
shorter than the min.
permissible length.

Check the command
format and set it
correctly.(*)

DASProtFail

03

The designated
number of data items
differs from the actual
number.

Check the number of
items and data and
make sure that they
agree.(*)

DASProtFail

05

An incorrect header
has been used. (Data
for another node was
received. Attempt was
made to send response
to broadcast address)

Check the header
parameters in the
command and be sure
the correct command
format is used.(*)

DASProtFail

11:
Parameter
error

00

The parameter in the
command data were
incorrect or the

Check the parameters
and be sure the socket
number is between 1

DASProtFail

Advertising