Server-Specific Error Codes

There are following server-specific error codes, shown in the table, that augment those
provided by the DAS Toolkit.

Error code

Logger Message

Log Flag

-10002

PLC timeout

DASProtFail

-10003

No Eth. Socket created DASProtFail

-10004

PLC Fatal Error(*)

DASProtFail


Note: Error code can be monitored in client application as Item’s $SYS$ErrorCode
value, correspondingly Logger Message can be monitored as Item’s $SYS$ErrorText
value.

(*) Fatal Error is set, if one of the following occasions permanently take place:

-

mismatch of command codes in DAServer request and PLC’s response messages,

-

controller response contains response error code with either Relay Error Flag (bit

#7 in response’s MRC) set to ON, or PC Fatal Error Flag (bit #7 in response’s SRC) set to
ON.

FINS Response Codes

Additionally, there are FINS command response codes (Main response code MRC and
Subcode SRC), generated by OMRON controllers, useful for communication
troubleshooting. The following is example of error logging created by Omron Ethernet
DAServer:

FINSSocket1.CV500: FINS command 0101 failed (error code 1101). Parameter error:
an incorrect memory area or unavailable expansion mem. area has been used.

In above example FINS command response code (1101) is to be interpreted as following:
MRC is 11 hex, SRC – 01 hex.

The accompanying table shows response codes, the server-specific strings generated by
the DAServer to the logger, as well as recommended remedies. (Suggestions usually
deals with configuring of OMRON PLC and/or FA network, yet several errors could be
caused by Omron Ethernet DAServer configuration errors).

Main Code
(Hex)

Sub-
code
(Hex)

Probable Cause

Remedy

Log Flag

00

00

Normal completion

-

-

00

01

Service was
interrupted.

Check transmission
area.

DASProtWarn

01: Local
node error

01

Local node not part of
network.

Add to network.

DASProtFail

02

Token time-out, node

Set the local node’s

DASProtFail