C/cpm2x plcs – Omron ETHERNET DIRECT DR 170 14 User Manual

Page 46

Advertising
background image

Klinkmann Automation Omron Ethernet DAServer

44


Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4 17014m14

C/CPM2x PLCs

The following table lists the supported item names for the C-series PLCs:

Memory Area

Prefix

Tag

Type

Range

Value

Range

Format

Suffix

CIO area

(Bit status)

IR

Discrete

IR0:00...IR511:15

or 0.00...511.15 (**)

0, 1

CIO area

(Word contents)

IR

Integer

IR0... IR511

or 0...511 (**)

(*)

u s b f g l

m d e c

Latching Relay area

(Bit status)

LR

Discrete

LR0:00... LR63:15

0, 1

Latching Relay area

(Word contents)

LR

Integer

LR0... LR63

(*)

u s b f g l

m d e c

Holding Relay area

(Bit status)

HR

Discrete

HR0:00... HR99:15

0, 1

Holding Relay area

(Word contents)

HR

Integer

HR0... HR99

(*)

u s b f g l

m d e c

Auxiliary Relay area

(Bit status)

AR

Discrete

AR0:00... AR27:15

0, 1

Auxiliary Relay area

(Word contents)

AR

Integer

AR0... AR27

(*)

u s b f g l

m d e c

Completion flags for

Timers/Counters(***)

TC

Discrete

TC0... TC511

0, 1

Present Values for

Timers/Counters

PV

Integer

PV0... PV511

(*)

u s b f g l

m d e c

Data Memory area

(Bit status)

DM

Discrete

DM0:0...DM9999:15

0, 1

Data Memory area

(Word contents)

DM

Integer

DM0...

DM9999

(*)

u s b f g l

m d e c


Item/point names, corresponding to Input/Output register area CIO, may be without
prefix.

(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default
value range for Integer Tag Type is unsigned integer.

(**) Represented memory area range is for C200HS type controller. For models C200H,
C1000H and C2000H - accessible memory area ranges are 0:00...255:15 for Discrete
items and 000...255 for Integer items.

(***) Read only

The following table lists the supported item names for the CPM2x PLCs:

Advertising