Klinkmann Automation Omron Ethernet DAServer

41


Omron Ethernet DAServer Ver 1.x User Manual Rev 1.4 17014m14

(****) Read only

The following examples show the correct format for item names for C200HX, C200HG,
C200HE PLCs and SYSMAC Board:

IR2:01 -

Internal Relay Area (Bit status), word address 2, bit number 1.

257

-

Special Relay Area (Word contents), word address 257

LR62.10

-

Link Relay Area (Bit status), word address 62, bit number 10

DM21

-

Data Memory Area (Word contents), word address 21

CV-series PLCs

The following table lists the supported item names for the CV-series PLCs:

Memory Area

Prefix

Tag

Type

Address Range

Value

Range

Suffix

Input/Output

register area CIO

(Bit status)

CIO

Discrete

CIO0:00...

CIO2555:15

or 0.00... 2555.15

0, 1

Input/Output

register area CIO

(Word contents)

CIO

Integer

CIO0... CIO2555

or

0…2555

(*)

u s b f g l

m d e c

Bus Link Area G

(Bit status)

G

Discrete

G0:00... G255:15

0, 1

Bus Link Area G

(Word contents)

G

Integer

G0... G255

(*)

u s b f g l

m d e c

Auxiliary Relay

area A (Bit status)

A

Discrete

A0:00... A511:15

0, 1

Auxiliary Relay

area A (Words)

A

Integer

A0... A511

(*)

u s b f g l

m d e c

Timer Completion

flags TIM (**)

T

Discrete

T0...T1023(***)

0, 1

Counter

Completion flags

CNT (**)

C

Discrete

C0... C1023(***)

0, 1

Timer Present

Value

PVT

Integer

PVT0...

PVT1023(***)

(*)

u s b f g l

m d e c

Counter Present

Value

PVC

Integer

PVC0...

PVC1023(***)

(*)

u s b f g l

m d e c

Data Memory area

(Bit status)

D

Discrete

D0:00…

D24575:15

(****)

0, 1

Data Memory area

(Word contents)

D

Integer

D0...D24575(****)

(*)

u s b f g l

m d e c

Transition Area

flags (**)

TN

Discrete

TN0...

TN1023(***)

0,1

Step Area Flag

status (**)

ST

Integer

ST0...ST1023

(***)

0,1,2,3