Toshiba DeviceNet Option DEV002Z-1 User Manual

Page 20

Advertising
background image

E6581281

f

- 19 -

Examples of Instance 101/151

Access the inverter parameter is enabled using byte 4 to 6 of this Instance.
Set the communication number of the parameter to byte 4, 5 (Index), and the value to byte 6, 7 (Data).

In case of the monitor parameter “FE**”,

the value becomes "communication number - 0x7000 (same as bit14, 15

set to 0)".

Read the parameter cmod (Command mode selection, communication number is 0003).

Instance

Byte

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Hex.

5, 4

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0x0003

Output Instance 101

7, 6

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Input Instance 151

5, 4

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0x0003

(cmod is set 0.)

7, 6

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0x0000

Read the parameter f268 (Initial value of UP/DOWN frequency).

Instance

Byte

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Hex.

5, 4

0

0

0

0

0

0

1

0

0

1

1

0

1

0

0

0

0x0268

Output Instance 101

7, 6

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Input Instance 151

5, 4

0

0

0

0

0

0

1

0

0

1

1

0

1

0

0

0

0x0268

(f268 is set 60.0Hz.)

7, 6

0

0

0

1

0

1

1

1

0

1

1

1

0

0

0

0

0x1770

Read the parameter fe04 (Voltage of DC bus).

Instance

Byte

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Hex.

5, 4

0

0

1

1

1

1

1

0

0

0

0

0

0

1

0

0

0x3E04

Output Instance 101

7, 6

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Input Instance 151

5, 4

0

0

1

1

1

1

1

0

0

0

0

0

0

1

0

0

0x3E04

(fe04 is 94.49%.)

7, 6

0

0

1

0

0

1

0

0

1

1

1

0

1

0

0

1

0x24E9

Write “60 (Hz)” to the parameter sr1 (Preset speed 1, communication number is 0018).

Instance

Byte

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Hex.

5, 4

1

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0x8018

Output Instance 101

7, 6

0

0

0

1

0

1

1

1

0

1

1

1

0

0

0

0

0x1770

5, 4

1

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0x8018

Input Instance 151 (OK)

7, 6

0

0

0

1

0

1

1

1

0

1

1

1

0

0

0

0

0x1770

Input Instance 151 (NG)

5, 4

1

1

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0xC018

(Error code

*

)

7, 6

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0x0001

About byte 0 - 3, refer to section 3.4.5.2.

*

Refer to following about the error code.

1

(= BN: 00000001):

: Data out of range

2

(= BN: 00000010):

: Bad address

3

(= BN: 00000011):

: Read only

4

(= BN: 00000100):

: Stop to modify or permission error

5

(= BN: 00000101):

: All other

Advertising