Communications-related parameters – Toshiba DeviceNet Option DEV002Z-1 User Manual

Page 8

Advertising
background image

E6581281

f

- 7 -

2.5. Communications-related parameters

In a network, VF-AS1/PS1 (DEV002Z) serves as a DeviceNet slave device. The
DEV002Z configuration is set by the following parameters.

The supported parameters for each drive and their allowable adjustment ranges are
defined in the appropriate Electronic Data Sheet (EDS) files. EDS files can be downloaded
via the internet from

http://www.inverter.co.jp/product/inv/vfas1/dev/index_i.htm

Parameter

Function

Adjustment range

Default setting

f830

*

Communication option

setting 1

Assembly

Object

0: Instance 20/70
1: Instance 21/71
2: Instance 100/150
3: Instance 101/151
4: Instance 102/152

0

f831

-

f846

Communication option

setting 2 - 13

Refer to section 3.4.5.6.

-

f851

Inverter operation at the

communications

loss action

(Network wire breaks)

0: Stop and Communication release
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command

(Operating at the preset speed operation
frequency set with f852)

0

f852

Preset speed operation

selection

0: None
1 to 15:Preset speed

0

f853

Monitoring of

communication device

station address

Displays the MAC ID number assigned using the DIP
switch.
0 to 63

1

f854

Monitoring of

communications

device’s baud rate

Displays the network communication speed set
with the DIP switch.
0: 125kbps
1: 250kbps
2: 500kbps

0

f899

Network option

reset setting

0: None

1: Resetting the DEV002Z and the inverter

0

* When the parameter is changed, the power must be cycled (or set f899 to 1) to the

VF-AS1/PS1 for the changes to take effect.

** When fmod or cmod is set to “Communication Input”, VF-AS1/PS1 drives without

Net Ref (Frequency link) or Net Ctrl (command link) at each Instance.