Toshiba DeviceNet Option DEV002Z-1 User Manual

Page 25

Advertising
background image

E6581281

f

- 24 -

3.4.6.8. FD01 (Inverter status (real time))

bit

Function

0

1

Note

0

FL

No output

Under output

-

1

EMG

No fault

Under fault

The rtry status and the trip
retention status are also
regarded as tripped statuses.

2

ALARM

No alarm

Under alarm

-

3

(Reserved)

-

-

-

4

tHr2(VF2+tH2)

Motor 1

(THR1)

Motor 2

(THR2)

THR1: thr
THR2: f173

5

PI

PI enable

PI off

-

6

ACC1/ACC2

Acc./Dec. 1

(AD1)

Acc./Dec. 2

(AD2)

AD1: acc, dec
AD2: f500, f501

7

DC braking

OFF

DC braking

-

8

Jog

OFF

JOG RUN

-

9

Fw/Reverse

Fwd. RUN

Rev. RUN

-

10

Run/stop

STOP

RUN

-

11

Free run (ST)

ST=ON

ST=OFF

-

12

Emergency stop

No EMG. Stop Under EMG. Stop

-

13

READY with ST/RUN

ST = ON and RUN = ON in
addition to “ready for operation”

*

14

READY without ST/RUN

-

15

**

Local/Remote

Remote

Local

-

*

Ready for operation: Initialization completed, not a stop due to a failure, no alarm issued, not moff,

not a forced stop due to ll, not a forced stop due to a momentary power failure.

**

This function is reserved in VF-AS1.

3.4.6.9. FD00 (Output frequency (real time))

The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.

Since the minimum unit is 0.01%,

0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)

Also about the following parameters, these are the same as this.

- FD22 (Feedback value of PID (real time)) ................................. Unit: 0.01Hz
- FD16 (PG feedback or Estimated speed (real time))................. Unit: 0.01Hz
- FD29 (Input power (real time))................................................... Unit: 0.01kW
- FD30 (Output power (real time)) ................................................ Unit: 0.01kW

3.4.6.10. FD03 (Output current (real time))

The output current is read into 0.01% of units and by the hexadecimal number.
For example, when the output current of the rated current 4.8A inverter is 50% (2.4A), 0x1388
(hexadecimal number) is read.

Since the minimum unit is 0.01%,

0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)

Also about the following parameters, these are the same as this.

- FD05 (Output voltage(real time) ................................................... Unit: 0.01% (V)
- FD04 (Voltage at DC bus (real time) ............................................ Unit: 0.01%(V)
- FD18 (Torque ............................................................................... Unit: 0.01% (Nm)

*

*

When the motor information connected to the inverter set to the parameter (f405 - f415), torque

monitor value "100%" is same as the rated torque of a motor in general.