3.4.5.6. How to use Instance 102/152

The purposes of instances 102/152 are adjustment by real time command transmission, and the monitor of an
operation state by using cyclic communication of DeviceNet.

Example 1: Command transmitting by output Instance 102

When you want to set "0xC400" to parameter fa06, set “1 (FA06)” to parameter f831.
And Since 0 and 1 byte of the output instance 102 supports the parameter f831, if "0xC400" is set up
here, "0xC400" will be set as fa06.

Example 2: State monitoring by the input instance 152.

When you want to monitor the output current, set “3 (FD03)” to parameter f841.
The value of the parameter fd03 specified as 0 and1 byte of the input instance 152 with the parameter
f841

is inputted.

f831

- f836 setup value

f841

- f846 setup value

0: No action
1: FA06 (ALCAN2 command 1)
2: FA23 (ALCAN2 command 2)
3: FA07 (ALCAN2 frequency command, 0.01Hz)
4: FA33 (Torque command, 0.01%)
5: FA50 (Terminal output)
6: FA51 (Analog output (FM) data from comm.)
7: FA52 (Analog output (AM) data from comm.)
8: F601 (Stall prevention level, %)
9: F441 (Power running torque limit 1 level, 0.01%)

10: F443 (Regenerative braking torque limit 1 level, 0.01%)
11: F460 (Speed loop proportional gain)
12: F461 (Speed loop stabilization coefficient)

0: No action

1: FD01 (Inverter status 1)

2: FD00 (Output frequency, 0.01Hz)

3: FD03 (Output current, 0.01%)

4: FD05 (Output voltage, 0.01%)

5: FC91 (Inverter alarm)

6: FD22 (PID feedback value, 0.01Hz)

7: FD06 (Input terminal status)

8: FD07 (Output terminal status)

9: FE36 (VI/II input)

10: FE35 (RR/S4 input)

11: FE37 (RX input)

12: FD04 (Input voltage (DC detection), 0.01%)

13: FD16 (Speed feedback (real-time value)

14: FD18 (Torque, 0.01%)

15: FE60 (My monitor)

16: FE61 (My monitor)

17: FE62 (My monitor)

18: FE63 (My monitor)

19: F880 (Free notes)

20: FD29 (Input power, 0.01kW)

21: FD30 (Output power, 0.01kW)

22: FE14 (Cumulative operation time, 0.01=1 hour)

23: FE40 (FM terminal output monitor)

24: FE41 (AM terminal output monitor)

VF-AS1/PS1

DEV002Z

"C400" is set as parameter fa06

Byte

Value

0

00

1

C4

2

...

3

...

...

...

DeviceNet Master

Parameter

Value

f831

1 (FA06)

f832

...

f833

...

...

...

Output Instance102

Parameter

Value

f841

3 (FD03)

f842

...

f843

...

...

...

The value of a parameter fd03 is outputted.

Byte

Value

0

xx

1

xx

2

...

3

...

...

...

Input Instance152

VF-AS1/PS1

DEV002Z

DeviceNet Master