1. T3H Overview


1.2 Differences between T3H and T3


The table below summarizes the differences between the T3H and T3. All other
functions supported by the T3 can also be supported by the T3H as same.

Item T3H

T3

Program memory capacity

32 k steps (PU325H)
64 k steps (PU326H)

32 k steps
(PU315 and PU325)

Built-in EEPROM

Yes
(PU325H and PU326H)

No (PU315)
Yes (PU325)

Programming instructions

All T3’s instructions plus
FUN042 D

/

FUN156 PID3
FUN232 FPID3
FUN239 SEND
FUN240 RECV

Execution speed (

µ

s)

0.09 / contact
0.18 / coil
0.9 / addition

0.15 / contact
0.3 / coil
1.5 / addition

Max. number of I/O modules
supported in local

76 modules
(when IF321 is used)

43 modules

System
operation

Timer interrupt interval
setting

1 to 1000 ms, 1 ms units

2 to 1000 ms, 1 ms units

Auto-RUN / standby
selection

Software setting
(system information)

Hardware switch
(RAM/ROM switch)

User data External I/O

(X/XW, Y/YW)

8192 points / 512 words

4096 points / 256 words

Auxiliary

register

(R/RW)

16000 points /
1000 words

8192 points / 512 words

Special

register

(S/SW)

4096 points / 256 words

Same as left

Timer (T./T)

1000 points
(proportion of 0.1s and
0.01s timer is user
definable)

512 points
(T000 - T063: 0.1s)
(T064 - T511: 0.01s)

Counter (C./C)

512 points

Same as left

Data register (D)

8192 words

Same as left

Link register (Z/W)
(for TOSLINE-S20)

16000 points /
2048 words
(bit access available for
leading 1000 words)

8192 points /
1024 words
(bit access available for
leading 512 words)

Link register (L/LW)
(for TOSLINE-F10)

4096 points / 256 words

Same as left

File register (F)

32768 words

8192 words

Index register
(I, J, K)

3 words

Same as left

Programming tool

T-PDS

T-PDS and HP911

Networking Ethernet,

TOSLINE-S20,
TOSLINE-F10,
RS-485 computer link

TOSLINE-S20,
TOSLINE-F10,
RS-485 computer link

Advertising