2. Expanded Functions

F

E

D

C

B 8

7 0

B

Abn Busy Status

0

TermSTS

B+1

Transmission error information (if TermSTS is H0B)



Inside the parameter:

Transfer parameter

S20LP

Ethernet

MID (network type)

2

3

CH (channel of self-station)

1 or 2 (max. two S20LP’s on T3H)

1 to 4 (max. four EN311’s on T3H)

Target station No.

1 to 64

0 (fixed)

Request command

0 (fixed)

H0021: Register read/write
(for other commands, refer to EN311
manual)

Transfer size
(number of words)

1 to 128
(max. 84 words for T or C register)
(designation across T511 and T512 is
not allowed)

1 to 485
(max. 323 words for T or C register)
(designation across T511 and T512 is
not allowed)

Register type

H0000: XW/YW register
H0001: W register
H0002: LW register
H0003: RW register
H0004: D register
H0005: F register (CPU)
H

∗∗

05: Expanded F register

(IC card, 8k words/bank,

∗∗

is bank No. 01 - 0F)

H

∗∗

06: Expanded F register

(IC card, 64k words/bank,

∗∗

is bank No. 01 - 02)

H0007: T register
H0008: C register
H0009: SW register

Leading address

Designates the leading register address to be transferred

Response time limit

Specifies the time limit of the response from target-station. (0.1 s units)
When the bit F is set to ON, the following default value is used.

S20LP ...... 4.1 s

Ethernet ... 30 s

Target-station IP address

N/A

Designates the IP address of the
target-station

Target-station UDP port No.

N/A

Designates the UDP port No. of the
target-station