User’s Manual

57

2. Expanded Functions



Transfer parameter table

Transfer object

Bank / CH

TYPE

Leading address

Transfer size

Status

flag

XW/YW register

0

H00

0 to 511 (T3H)
0 to 255 (T3)
0 to 63 (T2)

1 to 256

None

W register

0

H01

0 to 2047 (T3H)
0 to 1023 (T3/T2)

1 to 256

None

LW register

0

H02

0 to 255 (T3H/T3/T2)

1 to 256

None

RW register

0

H03

0 to 999 (T3H)
0 to 511 (T3)
0 to 127 (T2)

1 to 256

None

D register

0

H04

0 to 8191 (T3H/T3)
0 to 4095 (T2)

1 to 256

None

F register

0

H05

0 to 32767 (T3H)
0 to 8191 (T3)
0 to 1023 (T2)

1 to 256

None

Expanded F register

1 to 15

H05

0 to 8191 (T3H/T3/T2)

1 to 256

None

(IC memory card)

*1

1 or 2

H06

0 to 65535 (bank 1) (T3H)
0 to 57343 (bank 2) (T3H)

1 to 256

None

S20 scan memory

1 or 2

*2

H10

0 to 1023 (T3H/T3/T2)

1 to 256

Yes

*3

S20LP scan memory

*4

1 or 2

H10

0 to 4095 (T3H)

1 to 256

None

EEPROM (D register)

0

H20

0 to 8191 (T3H/T3)
0 to 4095 (T2)

Source (read)

1 to 256

None

Destination

(write)

1 to 128 (T3H)

1 to 64 (T3)
1 to 32 (T2)


*1) Two format types of the IC memory card is available. They are 8 k words/bank (type: H05) and 64 k

words/bank (type: H06). Type H06 is available only in the T3H.


*2) Channel 1 (CH1) only for the T2.

*3) The status flag is created only when S20 is designated as transfer source.

*4) S20LP is available only with the T3H. The S20LP does not have the scan healthy map. Therefore

status flag is not created for S20LP.