2. Expanded Functions


B+8

Initial status STS

F C 8 4 0

Initial operation mode

00 : Manual mode

01 : Auto mode

10 : Cascade mode

11 : (Reserve)


Direct / reverse selection

0 : Direct

1 : Reverse


B+9

MV upper limit MH (-25.00 to 125.00 %)

Data range: -2500 to 12500

B+10 MV lower limit ML (-25.00 to 125.00 %)

Data range: -2500 to 12500

B+11 MV differential limit DMV (0.00 to 100.00 %/

t)

Data range: 0 to 10000

B+12 Control interval setting n (1 to 32767 times)

Data range: 1 to 32767

Executes PID every n scan. Therefore, control interval

t = n

×

constant scan interval

(It is treated as n = 1 when n

0)



C

Manipulation value MV (-25.00 to 125.00 %)

Data range: -2500 to 12500

C+1

:

Internal work area

C+9


Operation


1. When the instruction input is OFF:

Initializes the PID3 instruction.

Operation mode is set as specified by B+8.

A+5 bit 0, 1

B+8 bit 0, 1

Auto mode SV is set as specified by B+4. ASV

ISV

Manual mode MV is set as current MV.

MMV

MV

Internal calculation data is initialized.

MV remains unchanged.

2. When the instruction input is ON:

Executes PID calculation every n scan which is specified by B+12. The following operation modes are
available according to the setting of A+5.

Auto mode
This is a normal PID control mode with ASV as set value.
Set value differential limit DSV, manipulation value upper/lower limit MH/ML and differential limit DMV
are effective.
Bump-less changing from auto mode to manual mode is available. (Manual mode manipulation value
MMV is over-written by current MV automatically. MMV

MV)