2. Expanded Functions



Ethernet


IP address = 133.113.98.10


T3H

T3H

(self-station)

(target-station)


F5000

D4000

F5001

D4001

F5199

D4199


When R0030 is ON, 200 words data starting with D4000 of the T3H on which EN311 (IP address =
133.113.98.10) is installed, is read and stored in F5000 and after.
When the operation is completed, the status is set in RW060 and instruction output comes ON.


Note

Keep the input ON until the output comes ON.

This instruction becomes error complete in the following cases. (ERF = S0051 is set to ON)
(1) Target station No. is invalid. (for S20LP)
(2) Invalid register designation. (In case of T and C registers, T

T and C

C is only possible)

(3) Source/destination register address range is out of valid range.
(4) Destination register is write-protected.
(5) Response time-out is occurred.
(6) If expanded F register is designated;

- when MMR setting is not made.

- when IC card is not installed.

- when IC card is used to store program.

- when IC card is write-protected. (for destination)

By using SW067, self-station’s register write-protect is available.

F 9 8 7 6 5 4 3 2 1 0

SW067 SW

C

T

F

D

RW

LW

W

YW


0: Write enable

1: Write protect


Resetting the status register (operand B) is necessary at the first scan.

When using the TOSLINE-S20LP or Ethernet module (EN311), read the manual for these network
modules.

Both F register in CPU and
expanded F register in IC card