2 essential pid (pid3), Expanded functions – Toshiba PROSEC T3H User Manual

Page 48

Advertising
background image

46

PROSEC T3H

2. Expanded Functions

2.4.2 Essential PID (PID3)

FUN 156

PID3

Essential PID


Expression

Input

─[ A PID3 B

C ]

─ Output

Function

Performs PID (Proportional, Integral, Derivative) control which is a fundamental method of feed-back control.
(Pre-derivative real PID algorithm)
This PID3 instruction has the following features.

For derivative action, incomplete derivative is used to suppress interference of high-frequency noise and to
expand the stable application range,

Controllability and stability are enhanced in case of limit operation for MV, by using digital PID algorithm
succeeding to benefits of analog PID.

Auto, cascade and manual modes are supported in this instruction.

Digital filter is available for PV.

Direct / reverse operation is selectable.

Execution condition

Input Operation Output

OFF Initialization

OFF

ON

Execute PID every setting interval

ON when

execution


Operand

Name

Device

Register

Con-

Index

X Y S L R Z T. C. I O X

W

Y

W

S

W

L

W

R

W

W T C D F I

W

O

W

I J K

stant

A Top of input

data

B Top of

parameter

C Top of

output data


Input data

Control parameter

Output data

A Process input value

PVC

B Proportional gain

K

P

C Manipulation value

MV

A+1 A-mode set value

ASV

B+1 Integral time

T

I

C+1 Last error

e

n-1

A+2 C-mode set value

CSV

B+2 Derivative time

T

D

C+2 Last derivative value

D

n-1

A+3 M-mode MV input

MMV

B+3 Dead-band

GP

C+3 Last PV

PV

n-1

A+4 MV tracking input

TMV

B+4 A-mode initial SV

ISV

C+4 Last SV

SV

n-1

A+5 Mode setting

MODE

B+5 Input filter constant

FT

C+5 Integral remainder

Ir

B+6 ASV differential limit

DSV

C+6 Derivative remainder

Dr

B+7 MMV differential limit DMMV

C+7 Internal MV

MV

n

A-mode: Auto mode

B+8 Initial status

STS

C+8 Internal counter

C

C-mode: Cascade mode

B+9 MV upper limit

MH

C+9 Control interval

∆∆∆∆

t

M-mode: Manual mode

B+10 MV lower limit

ML

B+11 MV differential limit

DMV

B+12 Control interval setting

n

Advertising