Expanded functions – Toshiba PROSEC T3H User Manual

Page 70

Advertising
background image

68

PROSEC T3H

2. Expanded Functions


Inside the parameter (cont’d):

Status S20LP

Ethernet

Abn

0: Normal complete
1: Error complete

Busy

0: Initial state
1: Transmission port busy

Status

0: Initial state
1: While send requesting
2: While waiting response
3: Complete

TermSTS

H00: Normal complete
H01: Register designation error
H02: Response time-out
H03: Parameter error
H04: Register write protect
H05: (Reserve)
H06: Module error (send time-out)
H07: No send channel
H08: Invalid station No.
H09: Transfer size error
H0A: Boundary error
H0B: Transmission error

Bit 7 indicates the error is occurred

H0C: I/O no answer error

whether self-station or target-station.

H0D: IC card designation error

0: Self-station

H0E: (Reserve)

1: Target-station

H0F: (Reserve)

Transmission error
information

When TermSTS is H0B, the error information is stored. (0 for other cases)
For detailed information, refer to the S20LP or EN311 manual.


Example

RW030

3

1

0

Ethernet, channel 1

RW031

33 (H21)

Request command H21: Register read/write

RW032

200

Transfer size: 200 words

RW033

5

Self-station F register

RW034

5000

Leading address: F5000

RW035

4

Target-station D register

RW036

4000

Leading address: D4000

RW037

50

Response time limit: 5 second

RW038

H71

H85

Target-station IP address:

RW039

H0A

H62

133.113.98.10 = H85.H71.H62.H0A

RW040

1024

Target-station UDP port No.: 1024


Send

requesting

RW060 0 0 1

0

0

RW061 0