31

2. Expanded Functions


2.2.3

Timer


The T3H has 1000 points of timer.

Function type

Type
code

Address range

Quantity

Expression

example

Timer register

T

000 - 999

1000 words

T670

Timer device

T.

000 - 999

1000 points

T.670


The proportion of the 0.01 s base and the 0.1 s base timers within this 1000 points
can be specified by user. This setting information is stored in the system information.

10 ms Timer Range Setting:

T000 - T [ ]

User setting (max. 999)













2.2.4

Link

register


The T3H has 2048 words of link register. This link register is prepared for the
TOSLINE-S20 (here called S20).

Function type

Type
code

Address range

Quantity

Expression

example

Link register

W

0000 - 2047

2048 words

W1500

Link device

Z

0000 - 999F

16000 points

Z847E


The link device Z corresponds to a bit in a link register W. The bit access as Z device
is available for the leading 1000 words of W register.

NOTE

T3H internally, the register ranges T000 to T511 and T512 to T999 are
handled separately. Therefore, index modification or table designation
across these ranges are not allowed.

For example)

├─[ T450 TMOV (100) D1000 ]-

Not allowed


├─[ T450 TMOV (62) D1000 ]-

Allowed

├─[ T512 TMOV (38) D1062 ]-