Table 5, Ainst, Current transformer – Trane RTWA 70-125 TON User Manual

Page 28

Advertising
background image

28

RLC-SVD03A-EN

Current Transformer

Table 5

Compressor Overload DIP Switch Settings

Compressor
Tons

Volts/Hz

RLA

Primary Turns
Through Current
Transformer

Current
Transformer

Extension

*

Overload Setting
Dip Sw/Decimal

12345

**

35

200/60

115

1

-02

01011/11

230/60

100

1

-01

11111/31

346/50

58

1

-10

01100/12

380/60

61

1

-10

10000/16

400/50

50

1

-10

00000/0

460/60

50

1

-10

00000/0

575/60

40

1

-01

01111/15

40

200/60

142

1

-02

11011/27

230/60

124

1

-02

10001/17

346/50

72

1

-01

00111/7

380/60

75

1

-01

01010/10

400/50

62

1

-10

10001/17

460/60

62

1

-10

10001/17

575/60

50

1

-01

11111/31

50

200/60

192

1

-03

11100/28

230/60

167

1

-03

10010/18

346/50

96

1

-01

11100/28

380/60

101

1

-02

00001/1

400/50

84

1

-01

10011/19

460/60

84

1

-01

10011/19

575/60

67

1

-02

10111/23

60

200/60

233

1

-04

10011/19

230/60

203

1

-04

01000/8

346/50

117

1

-02

01101/13

380/60

123

1

-02

10001/17

400/50

101

1

-02

00001/1

460/60

101

1

-02

00001/1

575/60

81

1

-03

10000/16

*The current transformer base part number is X13580253. The numbers in this column are suffixes of the base part number.

**On the DIP switch, 1=ON, O=OFF. The decimal value should be set in the compressor overload setting menu of the UCM. If the

DIP switch value does not match the decimal value entered into the UCM, the related compressor(s) will continue to run, but a
diagnostic will be initiated, both settings will be ignored, and the UCM will use the lowest possible trip setting value.