Module power and miscellaneous i/o – Trane RTWA 70-125 TON User Manual

Page 76

Advertising
background image

76

RLC-SVD03A-EN

Module Power and Miscellaneous I/O

J7-8,9

Step Load Solenoid

Normally open contact, closes to energize the Step Load Solenoid Valve.

J7-1, E7

Slide Valve Open
(Load Solenoid) Output

Triac Output, Refer to Checkout Procedure for MCSP Load/Unload
Outputs.

J7-1, E8

Slide Valve Close
(Unload Solenoid) Output

Triac Output, Refer to Checkout Procedure for MCSP Load/Unload
Outputs.

J8-1, 3

Fan Relay 1 Output

Normally open contact for Variable Speed Fan contactor control.

J8-1, 4

Fan Relay 2 Output

Normally open contact for fan contactor(s) control.

J8-1, 5

Fan Relay 3 Output

Same as above.

J8-1, 6

Fan Relay 4 Output

Same as above.

J9-6, 5

Variable Frequency
Fan Output PWM

10 Volt Peak, 10 Hz fundamental. Its average value can be read with a DC
voltmeter. Refer to Section 11 Variable Speed Fan System Trouble-
shooting.

J9-4, 3

Variable Frequency
Fan Fault Signal

Fault: 11 V (connector plugged on)
No Fault: 0 VDC (connector plugged on)
Refer to Section 11 Variable Speed Fan System Troubleshooting.

J9-2, 1

Not Used

N/A

Table 22

Compressor Module Normal Terminal Voltages (1 U4 and 1 U5)

Terminal
Designation

Description