Module power and miscellaneous i/o – Trane RTWA 70-125 TON User Manual

Page 51

Advertising
background image

RLC-SVD03A-EN

51

Module Power and Miscellaneous I/O

2.

Has its negative terminal tied to chassis ground.

If the intended source does not meet the above requirement, an isolation
module must be used

The 4-20mA/2-10VDC inputs may be tested in the following ways:

1.

Enable External Chilled Water Setpoint and/or External Current Limit Set-
point in the Operator Settings Menu. Advance display to Active Chilled
Water Setpoint or Active Current Limit Setpoint to observe the respective
setpoint in the Chiller Report.

2.

With all wiring in place, apply an external voltage or current to the Exter-
nal Chilled Water Setpoint inputs (TB1-4 & 5) or the External Current Limit
Setpoint (TB1-7 & 8). The voltage measured at the terminals and the
resulting setpoint, as read on the CLD, should agree with the

Table 17

for

Chilled Water Setpoint inputs and

Table 18

for Current Limit Setpoints

inputs. Be sure to wait long enough when reading the display as the val-
ues are slew rate limited.

3.

Disconnect all wiring to these inputs. The setpoints should slew back to
the chiller's Front Panel settings.

4.

Disconnect all wiring and install fixed resistors of values near those
shown in the following tables across TB1-3,5 or TBl-6,8. The resulting set-
points should agree with the table values.

Table 17

Input Values vs. External Chilled Water Setpoint

INPUTS
Resist (ohms)

Current (ma)

Voltage (Vdc)

Resulting Chilled
Water Setpt (F)±4F

94433

4.0

2.0

0.0

68609

5.2

2.6

5.0

52946

6.5

3.2

10.0

42434

7.7

3.9

15.0

34889

8.9

4.5

20.0

29212

10.2

5.1

25.0

24785

11.4

5.7

30.0

21236

12.6

6.3

35.0

18327

13.8

6.9

40.0

15900

15.1

7.6

45.0

13844

16.3

8.2

50.0

12080

17.5

8.8

55.0

10549

18.8

9.4

60.0