RLC-SVD03A-EN

7

General Information

Real time data for temperatures, diagnostics and control algorithms etc. are
made available to the CPM and the other modules for display and for input to
higher level functions. See

Electronic Expansion Valve Module (EXV) (1U3) on

page 58

for details.

Options Module (CSR) 1U2
The CSR module is an optional part of the system and employs communica-
tions circuits for interface to Trane Building Automation Systems, done
through 1C17. The CSR also provides inputs for hard wired external setpoints
and reset functions. Included are low voltage analog and digital input circuits.
See

Options Module (CSR) (1U2) on page 50

for details.

Clear Language Display (CLD) 1U6
The CLD Module provides an operator interface to the system, through a two
line, 40 character alphanumeric display. Three reports may be displayed and
various operating parameters may be adjusted by depressing a minimal
number of keys on the CLD. Also, chiller Start/Stop functions may be
performed at this keypad. See

Clear Language Display (CLD) 1U6 Keypad

Overview on page 42

for details.

Interprocessor Communication Bridge (IPCB) 1U7
The IPCB module allows connection of a Remote Clear Language Display
module to the UCM, for distances of up to 1500 feet. The Remote Clear
Language Display communicates with the UCM, utilizing the same IPC
protocol, and provides most of the same functions as the local CLD. The IPCB
then serves to protect the UCM's IPC if wires to the Remote CLD become
shorted or broken. See Section 2 and

on page 75

for details.