Setpoint priority, Table 18, Module power and miscellaneous i/o – Trane RTWA 70-125 TON User Manual

Page 52

Advertising
background image

52

RLC-SVD03A-EN

Module Power and Miscellaneous I/O

Setpoint Priority
There are many ways in which the Chilled Water and Current Limit setpoints
can be adjusted or reset when the Options Module is present in the Chiller
control system. The following flow charts show how these methods are prior-
itized and arbitrated under normal operating conditions. When abnormal
conditions are present, such as loss of Tracer communications or out of range
values on external setpoint inputs, the system will default to other methods.

Table 18

Input Values vs. External Current Limit Setpoint

Resist (ohms)

INPUTS
Current (ma)

Voltage (Vdc)

Resulting Current
Limit Setpt (%RLA)±5%

49000

4.0

2.0

40

29000

6.0

3.0

50

19000

8.0

4.0

60

13000

10.0

5.0

70

9000

12.0

6.0

80

6143

14.0

7.0

90

4010

16.0

8.0

100

2333

18.0

9.0

110

1000

20.0

10.0

120