Module Power and Miscellaneous I/O

I/O Terminals
For the checkout of the I/O, refer to the block diagram of the MCSP module in

Figure 22

and the Chiller Wiring Diagrams for both high and low voltage

circuits. All voltages are measured differentially between terminal pairs
specified unless otherwise indicated. The first terminal in the pair is the
positive (or hot) terminal. Voltages given are nominals and may vary by ±5%.
Unregulated Voltages (unreg) or 115 VAC voltages may vary by ±15%.

Table 22

Compressor Module Normal Terminal Voltages (1 U4 and 1 U5)

Terminal
Designation

Description
of Circuit

Normal Terminal Voltages
for Various Conditions

J1-4 to 3
or J1-2 to 1

IPC Communications

19.2 kbaud serial data, 5 volt signal level.
Refer to Interprocessor Communication Interface.

J2-2, 1

Manufacturing Address Use
Only

+5 VDC No connection intended.

J3-7, 6

External Circuit Lockout

Open = 12 VDC: ckt lockout
Closed 0 VDC: normal
(ckt. lockout' only if feature is enabled in Service Settings)
Must be jumpered if this feature is not used.

J3-4, 3

Transition Complete

Open = 12 VDC: pre-transition
Closed = 0 VDC: transition complete
(only used with reduced voltage starters)

J3-2, 1

Not Used

Must be jumpered.

J4-5, 4

Saturated Condenser
Refrigerant Temp

Refer to Temperature Sensor Checkout.

J4-3, 1

Entering Oil Temperature

Refer to Temperature Sensor Checkout.

J5-7, 6

Phase A Current
Transformer Input

Input for 100-400:0.1 Ratio CT using digital VOM
in diode test mode open circuit input should read between 1.0 to 1.5
Volts.
Refer to Current Transformer Checkout.

J5-5, 4

Phase B Current
Transformer Input

Same as above.

J5-2, 1

Phase C Current
Transformer Input

Same as above.

J6-1 or 2
to J6-4 or 5

Input Power

115 VAC, Refer to Power Supply in Module.
Power and Miscellaneous I/O.

E3, E4

Compressor Motor
Winding Temp
Thermostat.

Internally powered Isolated input.
Open = 16 Vac: high temp
Closed = 0 Vac: Ok temp

E5 to

High Pressure

Externally powered isolation transformer input,

J6-4 or 5

Cutout Input

2 VA, 115 Vac 115 volts input: normal 0 volts: trip

E5, J7-3

Compressor Contactor
Output

Normally open contact, closes for compressor start
Uses same power input as High Pressure Cutout input above.

J7-1, E6

Crankcase Heater Output

Normally closed contact, powers crankcase heater when compressor is
off.

J7-5,6

Transition Command Output

Normally open contact, closes to initiate Wye to Delta Starter transition if
configured for Reduced Voltage start.