Table 19

CSR Normal Terminal Voltages for Options Module 1U2

Terminal
Designation

Description
of Circuit

Normal Terminal Voltages
for Various Conditions

J1-4 to 3
or J1-2 to 1

IPC Communications

19.2 kbaud serial data, 5 volt signal level.
Refer to Interprocessor Communication Link (IPC).

J2-2, 1

Manufacturing
Address Use Only

+5 VDC No connection intended.

TB1-3

+5V Source for use with
Resistor programming of CW
setpoint

+5VDC open circuit with respect to chassis ground.

TB1-3, 5

Ext. Chilled Water Setpoint
(Resistive option)

Refer to

External Setpoint Inputs (4-20ma/2-10VDC) on page 50

.

TB1-4, 5

Ext. Chilled Water Setpoint
(Current or Voltage option)

Refer to

External Setpoint Inputs (4-20ma/2-10VDC) on page 50

.

TB1-6

+5V Source for use with
Resistor programming of CL
setpoint

+5VDC open circuit.

TB1-6, 8

Ext. Current Limit Setpoint
(Resistive option)

Refer to

External Setpoint Inputs (4-20ma/2-10VDC) on page 50

.

TB1-7, 8

Ext. Current Limit Setpoint
(Current or Voltage option)

Refer to

External Setpoint Inputs (4-20ma/2-10VDC) on page 50

.

TB1-9, 10

Unused

TB2A-1,2
or TB2B-3,4

Serial Comm.Input

Refer to Section 2, ICS Communications.

J6-1 or 2
to J6-4 or 5

Input Power

115 VAC, Refer to

Power Supply on page 41

.

Dip Switch
SW1-1

External Chilled Water Setpoint
Dip Switch

Off for 2-10 VDC input.
On for 4-20 mA input.

Dip Switch
SW1-2

External Current
Limit Setpoint
Dip Switch

Off for 2-10 VDC input.
On for 4-20 mA input.