Module power and miscellaneous i/o – Trane RTWA 70-125 TON User Manual

Page 49

Advertising
background image

RLC-SVD03A-EN

49

Module Power and Miscellaneous I/O

Table 16

CPM (Chiller) Nominal Terminal Input and Output (1U1)

Terminal
Designation

Description
of Circuit

Normal Terminal Voltages
for Various Conditions

J1-4 to 3 to CLD
J1-2 to 1 to 1U5

IPC Communications

19.2 kbaud serial data, 5 volt signal level.
Refer to Interprocessor Communication ([PC)

J2-2, 1

Manufacturing Address Use Only

+5 VDC No connection intended.

TB1-1, 2

Outdoor Air Temperature

Refer to Temperature Sensor Checkout

TB1-3, 4

Emergency Stop

open: 20.6 VDC unreg: Stopped
closed: 0 VDC: Normal
Must be jumpered if this feature is not used.

TB1-5, 6

NNS (Not Used)

open: 20.6 Vdc unreg: Normal
closed: 0 VDC: Setback

TB2-1, 2

ECWT (Not Used)

N/A

TB2-3, 4

LCWT (Not Used)

N/A

J3-5, 4

Entering Evaporator Water Temper-
ature

Refer to Temperature Sensor Checkout

J3-2, 1

Leaving Evaporator
Water Temperature

Refer to Temperature Sensor Checkout

J4-3, 1

Under/Over Voltage
Transformer Input

Refer to Under/Over Voltage Transformer
Checkout Procedure

J5-1 or 2
to J5-4 or 5

Input Power

115 VAC,

Power Supply on page 41

.

J6-3, 1

Auxiliary Temp. Input

Refer to Temperature Sensor Checkout

TB3-2, 1

Chilled Water
Flow Switch Input

open: 115VAC: No Flow
closed: < 5VAC: Flow (Software imposes a 6 second delay
to respond to opening or closing.

TB3-3,4

Chilled Water Demand Switch and
External Auto Stop

open: 115VAC: Stop
closed: < 5VAC: Auto

TB4-1, 2

Chiller Alarm or Alarm Ckt 1
(N.O. Contact)

Dry SPDT Contact closes on Alarm, intended for 115 VAC
customer control circuit.

TB4-1, 3

Chiller Alarm or Alarm Ckt 1
(N.O. Contact)

Dry SPDT Contact opens on Alarm, intended for 115 VAC
customer control circuit.

TB4-4, 5

Unit Running, Alarm Ckt 2, or
Ckt 1 Running
(N.O. Contact)

Dry SPDT Contact closes on Unit Running,
Alarm Ckt 2 or Ckt 1 Running, intended for
115 VAC customer control circuit.

TB4-6, 7

Maximum Capacity or Ckt 2 Running
(N.O. Contact)

Dry SPDT Contact closes on Maximum Capacity or Ckt 2
Running, intended for 115 VAC customer control circuit.

TB4-8, 9

Chilled Water Pump Starter
(N.O. Contact)

Dry SPST Contact closes when Chilled Water
Demand Switch is closed, opens after time
delay specified in UCM 115 VAC customer control circuit.

TB4-10, 11

Spare Relay}
(N.O.) Contact

Dry SPST contact. 115 VAC customer control circuit.