Table 6, Table 7, Current transformer – Trane RTWA 70-125 TON User Manual

Page 29

Advertising
background image

RLC-SVD03A-EN

29

Current Transformer

Table 6

Trip Times Vs. % Current

MOTOR CURRENT
(% RATED RLA)

MINIMUM

TRIP TIME (SEC)
NOMINAL

MAXIMUM

127.7 or below

No trip

No Trip

No Trip

132.0

27.2

No Trip

No Trip

132.1

27.2

30.08

No Trip

140.0 (must trip pt.)

22.8

25.28

28.09

150.0

18.8

20.48

22.89

160.0

16.0

17.28

19.29

170.0

14.0

15.28

16.89

180.0

12.4

13.28

14.89

190.0

11.2

12.08

13.29

200.0

10.4

10.88

12.09

210.0

9.6

10.08

10.89

220.0

8.8

9.28

10.09

230.0

8.0

8.48

9.69

240.0

7.6

8.08

8.89

250.0

7.2

7.68

8.49

260.0

6.8

6.88

7.69

270.0

6.4

6.88

7.29

280.0

6.0

6.48

6.89

290.0

5.6

6.08

6.89

300.0

4.0

5.68

6.49

300.1

4.0

4.08

6.49

310.2 or above

4.0

4.08

4.49

Table 7

Current Transformers Ratings and Resistance

EXT

*

*The current transformer base part number is X13580253. The

numbers in this column are suffixes of the base part number.

RATING
USABLE

RANGE

RESISTANCE
OHMS + 10%

01

100A

66.67 -100A

23.5

02

150A

100 - 150A

35.0

03

200A

134 - 200A

46.0

04

275A

184 -275A

67.0

05

400A

267 - 400A

68.0

09

50A

33.37 - 50A

11.5

10

75A

50 - 75A

17.0

Advertising
This manual is related to the following products: