Figure 6 manual slide valve diagnostic flow chart, Checkout procedure for mcsp step load output, Compressor capacity – Trane RTWA 70-125 TON User Manual

Page 39

Advertising
background image

RLC-SVD03A-EN

39

Compressor Capacity

pressure, then the Slide Valve is bound.

5.

If cylinder cavity pressure does not decrease or is at suction pressure
before the Unload toggle switch was closed, the problem lies with either
the solenoid coil or valve.

6.

Check coil

7.

If coil checks out, change the valve.

NOTE:

Refer to the Flow Chart in

Figure 6

.

Checkout Procedure for MCSP Step Load Output

The MCSP controls the step load solenoid valve on the respective
compressor with a 115 VAC dry contact output relay. This differs from the
Load/Unload solenoid output, which is from a triac (solid state relay). Refer to
the Chiller Control Wiring diagrams and the Component Layout Drawings for
the following procedure.

Unload:

10. Manually unload compressor in short increments.

11. Does RLA Decrease?

Check UCM

Stop

Replace

12. Does Cavity Press

decrease to a level
close to suct pressure?

Slide valve mechanism bound

13. Does Magnetic Field on

Solenoid Coil exist?

Solenoid valve mechanism bound

14. Is wiring to valve OK?

Check for open solenoid coil

15. Repair and reverify.

Figure 6

Manual Slide Valve Diagnostic Flow Chart

No

Yes

Bad

Good

Yes

No

Yes

No

Yes

No