Table GD - 1 — General Data

Convertible Units

Convertible Units

Convertible Units

Convertible Units

Convertible Units

TSC060AD

TSC072AD

TSC090AD

TSC102AD

TSC120AD

Cooling Performance

1

Gross Capacity - kW (MBh)

18.2 (62.0)

23.2 (79.0)

26.7 (91.0)

31.1 (106.0)

34.9 (119.0)

COP (EER)

2

2.99 (10.2)

3.08 (10.5)

3.02 (10.3)

3.02 (10.3)

2.99 (10.2)

Nominal Airflow - m

3

/h (cfm)

3400 (2000)

4080 (2400)

5100 (3000)

5780 (3400)

6800 (4000)

Rated Airflow - m

3

/h (cfm)

3400 (2000)

3570 (2100)

4460 (2625)

5100 (3000)

5950 (3500)

Net Capacity - kW (MBh)

17.3 (59.0)

22.0 (75.0)

25.2 (86.0)

29.9 (102.0)

33.1 (113.0)

System Power - kW

5.78

7.14

8.35

9.90

11.08

Compressor

Number - Type

1-Climatuff Scroll

1-Trane 3-D Scroll

1-Trane 3-D Scroll

2-Climatuff Scroll

2-Climatuff Scroll

Outdoor Sound Rating - dB

3

80

85

85

83

79

Outdoor Coil - Type

Lanced

Lanced

Lanced

Lanced

Lanced

Tube Size - in. OD

0.3125

0.3125

0.3125

0.3125

0.3125

Face Area - m

2

(sq ft)

1.02 (10.96)

1.29 (13.88)

1.29 (13.88)

1.75 (18.89)

2.41 (25.92)

Rows / FPI

3 / 17

2 / 17

2 / 17

2 / 17

2 / 17

Indoor Coil - Type

Lanced

Lanced

Lanced

Lanced

Lanced

Tube Size OD - in.

0.3125

0.3125

0.3125

0.3125

0.3125

Face Area - m

2

(sq ft)

0.62 (6.68)

0.92 (9.89)

0.92 (9.89)

1.15 (12.36)

1.15 (12.36)

Rows / FPI

3 / 16

2 / 16

3 / 16

3 / 16

4 / 16

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Drain Connection No. / Size - in.

1 / 0.75 NPT

1 / 0.75 NPT

1 / 0.75 NPT

1 / 0.75 NPT

1 / 0.75 NPT

Outdoor Fan - Type

Propeller

Propeller

Propeller

Propeller

Propeller

No. Used / Diameter - in.

1 / 22

1 / 26

1 / 26

1 / 26

1 / 26

Drive Type / No. Speeds

Direct / 1

Direct / 1

Direct / 1

Direct / 1

Direct / 1

CFM

2900

5100

5200

5500

5800

No. Motors / kW (HP)

1 / 0.30 (0.40)

1 / .56 (0.75)

1 / .56 (0.75)

1 / .56 (0.75)

1 / .56 (0.75)

Motor RPM

950

950

950

950

950

Belt Drive Indoor Fan - Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

1

1

Fan Diameter x Width - mm (in.)

280 X 280 (11 x 11)

305 X 305 (12 x 12)

305 X 305 (12 x 12)

381 X 381 (15 x 15)

381 X 381 (15 x 15)

Drvie Type / No. Speeds

Belt / Variable Speed

Belt / Variable Speed

Belt / Variable Speed

Belt / Variable Speed

Belt / Variable Speed

No. Motors

1

1

1

1

1

Standard Motor Power - kW (HP)

1.1 (1.5)

1.1 (1.5)

1.5 (2.0)

1.5 (2.0)

2.2 (3.0)

Oversized Motor Power - kW (HP)

-

1.5 (2.0)

2.2 (3.0)

2.2 (3.0)

-

Motor RPM - Standard / Oversized

1450 / -

1450 / 1450

1450 / 2850

1450 / 2850

2850 / -

Motor Frame Size

56

56

56

56

56

Filters - Type Furnished

Throwaway

Throwaway

Throwaway

Throwaway

Throwaway

(No.) Size Reccommended - mm

(2) 508 X 762 X 25

(4) 406 X 635 X 50

(4) 406 X 635 X 50

(4) 508 X 635 X 50

(4) 508 X 635 X 50

(No.) Size Reccommended - in.

(2) 20 X 30 X 1

(4) 16 X 25 X 2

(4) 16 X 25 X 2

(4) 20 X 25 X 2

(4) 20 X 25 X 2

Refrigerant Charge - kg (lbs) of R-22

4

3.7 (8.2)

3.7 (8.2)

4.5 (10.0)

Circuit 1 - 3.8 (8.3)

Circuit 1 - 3.4 (7.5)

Circuit 2 - 2.0 (4.4)

Circuit 2 - 3.3 (7.3)

Notes:
1. Cooling Performance is rated at 35.0 C (95 F) ambient, 26.7 C (80 F) entering dry bulb, 19.4 C (67 F) entering wet bulb. Gross capacity does not include the effect of fan motor

heat. Net capacity includes the effect of fan motor heat. Units are suitable for operation to ± 20 % of nominal airflow.

2. EER are rated at ARI conditions.
3. Outdoor Sound rating shown is tested in accordance with ARI Standard 270. For more information refer to Performance Data Table "Sound Power Level".
4. Refrigerant charge is an approcimate value. For a more precise value, see unit nameplate and service literature.

Advertising