Performance data – Trane TSC060-120 User Manual

Page 22

Advertising
background image

22

RT-PRC016-EN

Performance
Data

Table PD-9a — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-1/2 HP Standard Motor & Low Static Drive

1-1/2 HP Standard Motor & Drive

1920

-

-

565

0.31

627

0.39

679

0.45

726

0.52

771

0.60

814

0.69

857

0.77

899

0.85

939

0.93

2160

566

0.35

609

0.41

663

0.48

716

0.57

762

0.64

804

0.72

843

0.80

883

0.90

922

0.99

960

1.08

2400

619

0.47

660

0.54

701

0.60

751

0.69

798

0.78

839

0.87

877

0.95

914

1.04

950

1.14

984

1.24

2640

672

0.61

710

0.68

745

0.76

788

0.83

833

0.93

875

1.04

914

1.13

949

1.22

984

1.31

1016

1.42

2880

726

0.77

762

0.86

795

0.94

828

1.02

869

1.11

911

1.21

950

1.33

986

1.44

1019

1.53

1051

1.63

1-1/2 HP Standard Motor & Drive

1-1/2 HP Std Motor & Hi Static Drive

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-1/2 HP Standard Motor & Hi Static Drive

1920

978

1.02

1015

1.11

1051

1.20

1086

1.30

1118

1.39

2160

996

1.17

1034

1.27

1069

1.36

1103

1.46

1136

1.56

2400

1020

1.35

1055

1.45

1089

1.55

1122

1.66

1154

1.76

2640

1049

1.53

1081

1.65

1113

1.76

1144

1.87

1176

1.98

2880

1081

1.74

1112

1.86

1141

1.97

1170

2.10

1199

2.22

2 HP Over-Sized Motor & High Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-9 — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Standard Motor & Low Static Drive

1.12 Nom kW Standard Motor & Drive

3260

-

-

565

0.23

627

0.29

679

0.34

726

0.39

771

0.45

814

0.51

857

0.57

899

0.63

939

0.70

3670

566

0.26

609

0.31

663

0.36

716

0.42

762

0.48

804

0.54

843

0.60

883

0.67

922

0.74

960

0.81

4080

619

0.35

660

0.40

701

0.45

751

0.51

798

0.59

839

0.65

877

0.71

914

0.78

950

0.85

984

0.93

4490

672

0.45

710

0.51

745

0.56

788

0.62

833

0.69

875

0.77

914

0.85

949

0.91

984

0.98

1016

1.06

4890

726

0.58

762

0.64

795

0.70

828

0.76

869

0.82

911

0.91

950

0.99

986

1.07

1019

1.14

1051

1.22

1.12 Nom kW Standard Motor & Drive

1.12 Nom kW Standard Motor

& Hi Static Drive

External Static Pressure (Pascals)

275

300

325

350

375

CFM

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Standard Motor & Hi Static Drive

3260

978

0.76

1015

0.83

1051

0.90

1086

0.97

1118

1.04

3670

996

0.87

1034

0.95

1069

1.02

1103

1.09

1136

1.17

4080

1020

1.00

1055

1.08

1089

1.16

1122

1.23

1154

1.31

4490

1049

1.14

1081

1.23

1113

1.31

1144

1.40

1176

1.48

4890

1081

1.30

1112

1.38

1141

1.47

1170

1.57

1199

1.66

1.50 Nom kW Over-Sized Motor & Hi Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.