RT-PRC016-EN

Performance
Data

Table PD-10 — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.50 Nom kW Standard Motor & Low Static Drive

1.50 Nom kW Standard Motor & Drive

4080

-

-

-

-

-

-

701

0.47

750

0.54

794

0.60

834

0.67

873

0.73

909

0.80

945

0.87

4590

-

-

-

-

699

0.53

743

0.59

787

0.66

830

0.74

871

0.82

908

0.89

943

0.96

977

1.04

5100

-

-

703

0.61

747

0.68

789

0.74

827

0.82

867

0.90

906

0.98

944

1.06

980

1.15

1013

1.23

5610

713

0.69

755

0.77

797

0.85

836

0.92

873

1.00

908

1.08

944

1.17

980

1.26

1016

1.35

1050

1.45

6120

771

0.88

809

0.96

848

1.06

885

1.14

921

1.22

954

1.30

986

1.39

1019

1.49

1052

1.58

1085

1.69

External Static Pressure (Pascals)

275

300

325

350

375

CFM

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.50 Nom kW Std Motor

1.50 Nom kW Standard Motor

& Drive

& Hi Static Drive

4080

980

0.95

1013

1.02

1046

1.10

1076

1.17

1106

1.25

4590

1010

1.11

1043

1.19

1074

1.27

1105

1.36

1134

1.44

5100

1045

1.31

1076

1.39

1105

1.47

1134

1.56

1163

1.65

5610

1081

1.54

1111

1.63

1141

1.72

1168

1.80

1197

1.90

6120

1116

1.79

1148

1.89

1177

1.99

1204

2.08

1232

2.18

2.24 Nom kW Over-Sized Motor
& Hi Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

1.50 Nom kW Standard Motor
& Hi Static Drive

← ← ← ← ←

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-10a — Belt Drive Evaporator Fan Performance -TSC090AD - Downflow Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2 HP Standard Motor & Low Static Drive

2 HP Standard Motor & Drive

2400

-

-

-

-

-

-

701

0.63

750

0.72

794

0.81

834

0.90

873

0.98

909

1.08

945

1.17

2700

-

-

-

-

699

0.70

743

0.79

787

0.89

830

0.99

871

1.09

908

1.19

943

1.29

977

1.39

3000

-

-

703

0.81

747

0.91

789

0.99

827

1.10

867

1.20

906

1.31

944

1.43

980

1.54

1013

1.65

3300

713

0.93

755

1.03

797

1.15

836

1.24

873

1.34

908

1.45

944

1.57

980

1.69

1016

1.82

1050

1.94

3600

771

1.19

809

1.29

848

1.42

885

1.53

921

1.63

954

1.74

986

1.87

1019

1.99

1052

2.13

1085

2.26

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2 HP Standard Mtr

2 HP Standard Motor &

& Drive

Hi Static Drive

2400

980

1.27

1013

1.37

1046

1.47

1076

1.57

1106

1.68

2700

1010

1.49

1043

1.60

1074

1.71

1105

1.82

1134

1.93

3000

1045

1.76

1076

1.87

1105

1.98

1134

2.09

1163

2.21

3300

1081

2.06

1111

2.18

1141

2.30

1168

2.42

1197

2.55

3600

1116

2.39

1148

2.53

1177

2.66

1204

2.79

1232

2.93

3 HP Over-Sized Mtr & Hi Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

2 HP Standard Motor
& Hi Static Drive

← ← ← ← ←

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.