Performance data – Trane TSC060-120 User Manual

Page 28

Advertising
background image

28

RT-PRC016-EN

Performance
Data

Table PD-15 — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

2.24 Nom kW Standard Motor & Low Static Drive

2.24 Nom kW Standard Motor & Drive

5440

-

-

691

0.67

730

0.75

771

0.84

807

0.94

844

1.04

886

1.16

926

1.28

965

1.41

1000

1.53

6120

729

0.84

761

0.91

792

0.99

829

1.08

865

1.19

898

1.30

930

1.41

965

1.53

1002

1.67

1038

1.81

6800

802

1.13

833

1.22

860

1.29

890

1.38

923

1.50

956

1.62

986

1.73

1015

1.85

1044

1.98

1077

2.12

7480

876

1.49

905

1.58

931

1.67

955

1.75

983

1.86

1014

1.99

1045

2.12

1072

2.25

1098

2.37

1125

2.51

8160

950

1.91

977

2.02

1002

2.11

1025

2.20

1048

2.30

1074

2.42

1102

2.56

1131

2.71

1156

2.84

1181

2.98

2.24 Nom kW Standard Motor & High Static Drive

External Static Pressure (Pascals)

275

300

325

350

375

400

425

450

475

500

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

2.24 Nom kW Std Mtr & Drive

5440

1029

1.64

1057

1.75

1084

1.86

1108

1.96

1132

2.06

1155

2.17

1177

2.27

1198

2.37

1219

2.48

1239

3.46

6120

1072

1.95

1106

2.10

1134

2.22

1160

2.35

1185

2.47

1209

2.59

1231

2.70

1252

2.82

1274

2.94

1295

4.10

6800

1111

2.28

1143

2.43

1174

2.58

1204

2.74

1232

2.90

1260

3.05

1283

3.18

1306

3.32

-

-

-

-

7480

1152

2.65

1182

2.81

1211

2.97

1241

3.14

1270

3.31

-

-

-

-

-

-

-

-

-

-

8160

1205

3.12

1229

3.27

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2.24 Nom kW Standard Motor & High Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Table PD-15a — Belt Drive Evaporator Fan Performance -TSC120AD - Horizontal Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3 HP Standard Motor & Low Static Drive

3 HP Standard Motor & Drive

3200

-

-

691

0.89

730

1.00

771

1.13

807

1.26

844

1.39

886

1.55

926

1.72

965

1.89

1000

2.06

3600

729

1.13

761

1.22

792

1.32

829

1.45

865

1.60

898

1.74

930

1.89

965

2.06

1002

2.24

1038

2.43

4000

802

1.52

833

1.63

860

1.73

890

1.86

923

2.01

956

2.17

986

2.32

1015

2.48

1044

2.65

1077

2.85

4400

876

1.99

905

2.12

931

2.24

955

2.35

983

2.49

1014

2.66

1045

2.84

1072

3.01

1098

3.18

1125

3.36

4800

950

2.56

977

2.70

1002

2.84

1025

2.96

1048

3.08

1074

3.24

1102

3.43

1131

3.63

1156

3.81

1181

4.00

3 HP Standard Motor & High Static Drive

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3 HP Std Mtr & Drive

3200

1029

2.20

1057

2.35

1084

2.49

1108

2.63

1132

2.77

1155

2.91

1177

3.05

1198

3.18

1219

3.32

1239

3.46

3600

1072

2.62

1106

2.81

1134

2.98

1160

3.15

1185

3.31

1209

3.47

1231

3.63

1252

3.78

1274

3.94

1295

4.10

4000

1111

3.05

1143

3.26

1174

3.47

1204

3.68

1232

3.88

1260

4.09

1283

4.27

1306

4.46

-

-

-

-

4400

1152

3.55

1182

3.76

1211

3.99

1241

4.21

1270

4.44

-

-

-

-

-

-

-

-

-

-

4800

1205

4.19

1229

4.39

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

3 HP Standard Motor & High Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Advertising