Performance data – Trane TSC060-120 User Manual

Page 21

Advertising
background image

21

RT-PRC016-EN

Performance
Data

Table PD-8 — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Standard Motor & Low Static Drive

1.12 Nom kW Standard Motor & Drive

3260

-

-

-

-

573

0.25

630

0.30

680

0.36

726

0.41

769

0.47

811

0.52

851

0.58

889

0.65

3670

-

-

548

0.26

602

0.31

656

0.37

706

0.43

751

0.49

792

0.55

832

0.61

871

0.67

908

0.74

4080

-

-

584

0.33

635

0.38

682

0.45

732

0.51

777

0.58

818

0.64

856

0.71

893

0.77

930

0.84

4490

569

0.35

621

0.42

670

0.47

715

0.54

758

0.60

802

0.68

845

0.75

883

0.82

919

0.89

953

0.96

4890

612

0.45

660

0.51

706

0.58

749

0.64

789

0.71

830

0.79

870

0.87

909

0.95

945

1.02

979

1.10

External Static Pressure (Pascals)

275

300

325

350

375

CFM

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Std Motor

1.12 Nom kW Standard Motor

& Drive

& Hi Static Drive

3260

925

0.71

960

0.77

994

0.83

1026

0.89

1057

0.95

3670

944

0.81

978

0.87

1010

0.94

1043

1.01

1073

1.08

4080

964

0.91

998

0.99

1030

1.06

1063

1.14

1092

1.21

4490

986

1.04

1019

1.11

1051

1.19

1082

1.27

1112

1.35

4890

1011

1.18

1043

1.26

1073

1.34

1103

1.42

1133

1.51

1.50 Nom kW Over-Sized Motor

& Hi Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464

1.12 Nom kW Standard Motor
& Hi Static Drive

← ← ← ← ←

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-8a — Belt Drive Evaporator Fan Performance -TSC072AD - Downflow Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-1/2 HP Standard Motor & Low Static Drive

1-1/2 HP Standard Motor & Drive

1920

-

-

-

-

573

0.34

630

0.41

680

0.48

726

0.55

769

0.62

811

0.70

851

0.78

889

0.87

2160

-

-

548

0.35

602

0.42

656

0.50

706

0.58

751

0.65

792

0.73

832

0.81

871

0.90

908

0.99

2400

-

-

584

0.45

635

0.52

682

0.60

732

0.69

777

0.77

818

0.86

856

0.95

893

1.04

930

1.13

2640

569

0.47

621

0.56

670

0.64

715

0.72

758

0.81

802

0.91

845

1.01

883

1.10

919

1.20

953

1.29

2880

612

0.60

660

0.69

706

0.78

749

0.86

789

0.96

830

1.06

870

1.16

909

1.27

945

1.37

979

1.48

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-1/2 HP Standard Mtr

& Drive

1920

925

0.95

960

1.03

994

1.11

1026

1.19

1057

1.27

2160

944

1.08

978

1.17

1010

1.26

1043

1.36

1073

1.44

2400

964

1.22

998

1.32

1030

1.42

1063

1.53

1092

1.63

2640

986

1.39

1019

1.49

1051

1.60

1082

1.71

1112

1.81

2880

1011

1.58

1043

1.69

1073

1.79

1103

1.90

1133

2.02

2 HP Over-Sized Mtr & Hi Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500

1-1/2 HP Standard Motor
& Hi Static Drive

← ← ← ← ←

1-1/2 HP Standard Motor &
Hi Static Drive

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.