Performance data – Trane TSC060-120 User Manual

Page 19

Advertising
background image

19

RT-PRC016-EN

Table PD-6 — Belt Drive Evaporator Fan Performance - TSC060AD - Downflow Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Standard Motor & Low Static Drive

1.12 Nom kW Standard Motor & Drive

2720

-

-

703

0.27

757

0.31

806

0.35

854

0.39

899

0.43

944

0.49

985

0.54

1023

0.59

1060

0.64

3060

706

0.32

760

0.35

815

0.40

861

0.45

904

0.49

947

0.54

988

0.58

1028

0.64

1067

0.70

1104

0.76

3400

773

0.43

821

0.46

873

0.51

918

0.57

958

0.62

998

0.67

1036

0.71

1073

0.76

1111

0.82

1147

0.89

3740

840

0.56

885

0.60

930

0.65

977

0.71

1016

0.77

1053

0.82

1089

0.88

1124

0.93

1158

0.98

1191

1.03

4080

909

0.71

950

0.76

990

0.80

1034

0.87

1074

0.93

1110

1.00

1143

1.06

1177

1.12

1209

1.17

1241

1.23

External Static Pressure (Pascals)

275

300

325

350

375

CFM

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.12 Nom kW Standard Motor & Drive

2720

1093

0.69

1126

0.74

1160

0.79

1190

0.84

1222

0.90

3060

1138

0.82

1171

0.87

1203

0.93

1232

0.98

1262

1.04

3400

1182

0.96

1215

1.02

1246

1.09

1276

1.15

1306

1.21

3740

1226

1.10

1258

1.17

1290

1.25

-

-

-

-

4080

1272

1.29

-

-

-

-

-

-

-

-

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

1.12 Nom kW Standard Motor &
Hi Static Drive

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-6a — Belt Drive Evaporator Fan Performance -TSC060AD - Downflow Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-1/2 HP Standard Motor & Low Static Drive

1-1/2 HP Standard Motor & Drive

1600

-

-

703

0.36

757

0.41

806

0.47

854

0.52

899

0.58

944

0.65

985

0.73

1023

0.79

1060

0.86

1800

706

0.42

760

0.47

815

0.54

861

0.60

904

0.66

947

0.72

988

0.78

1028

0.86

1067

0.94

1104

1.02

2000

773

0.57

821

0.62

873

0.69

918

0.76

958

0.83

998

0.90

1036

0.96

1073

1.02

1111

1.10

1147

1.19

2200

840

0.75

885

0.80

930

0.87

977

0.95

1016

1.03

1053

1.10

1089

1.17

1124

1.24

1158

1.31

1191

1.39

2400

909

0.96

950

1.02

990

1.08

1034

1.16

1074

1.25

1110

1.34

1143

1.419

1177

1.50

1209

1.57

1241

1.65

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-1/2 HP Standard Motor & Drive

1600

1093

0.92

1126

0.99

1160

1.06

1190

1.13

1222

1.20

1800

1138

1.10

1171

1.17

1203

1.25

1232

1.32

1262

1.39

2000

1182

1.28

1215

1.37

1246

1.46

1276

1.54

1306

1.62

2200

1226

1.48

1258

1.57

1290

1.67

-

-

-

-

2400

1272

1.73

-

-

-

-

-

-

-

-

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451

1-1/2 HP Standard Motor &
Hi Static Drive

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Performance
Data