Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.50 Nom kW Std Motor & Low Static Drive

1.50 Nom kW Standard Motor & Drive

4080

-

-

673

0.42

718

0.47

769

0.54

814

0.61

855

0.67

893

0.73

929

0.81

965

0.88

999

0.96

4590

702

0.51

738

0.56

773

0.62

817

0.68

862

0.76

904

0.85

941

0.92

975

0.98

1009

1.06

1041

1.14

5100

771

0.68

805

0.74

837

0.81

870

0.87

912

0.94

951

1.03

989

1.12

1025

1.21

1056

1.28

1088

1.36

5610

842

0.89

873

0.96

903

1.03

930

1.10

963

1.17

1000

1.25

1037

1.34

1073

1.45

1106

1.55

1136

1.63

6120

913

1.14

942

1.22

970

1.30

996

1.37

1021

1.45

1052

1.52

1086

1.61

1121

1.71

1153

1.82

1184

1.93

1.50 Nom kW Standard Motor & Drive

1.50 Nom kW Standard Motor &

2.24 Nom kW OS

Hi Static Drive

Motor & Hi Static Drive

External Static Pressure (Pascals)

275

300

325

350

375

CFM

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.50 Nom kW Standard Motor & Hi Static Drive

4080

1035

1.04

1070

1.12

1104

1.19

1137

1.27

1168

1.35

4590

1073

1.22

1104

1.31

1136

1.40

1167

1.48

1198

1.57

5100

1117

1.44

1146

1.53

1176

1.62

1205

1.72

1233

1.82

5610

1165

1.72

1194

1.80

1220

1.88

1248

1.98

1275

2.08

6120

1215

2.04

1242

2.13

1269

2.22

1295

2.31

1319

2.40

2.24 Nom kW Over-Sized Motor & Hi Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2 HP Std Motor & Low Static Drive

2 HP Standard Motor & Drive

2400

-

-

673

0.56

718

0.63

769

0.72

814

0.82

855

0.90

893

0.98

929

1.08

965

1.18

999

1.29

2700

702

0.68

738

0.76

773

0.83

817

0.92

862

1.02

904

1.13

941

1.23

975

1.32

1009

1.42

1041

1.52

3000

771

0.91

805

1.00

837

1.08

870

1.17

912

1.26

951

1.38

989

1.51

1025

1.62

1056

1.72

1088

1.82

3300

842

1.19

873

1.29

903

1.38

930

1.47

963

1.57

1000

1.68

1037

1.80

1073

1.94

1106

2.08

1136

2.19

3600

913

1.53

942

1.63

970

1.74

996

1.84

1021

1.94

1052

2.04

1086

2.16

1121

2.29

1153

2.44

1184

2.59

2 HP Standard Motor & Drive

2 HP Std Motor & Hi Static Drive

3 HP Over-Sized Motor
& Hi Static Drive

← ← ← ← ←

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2 HP Standard Motor & Hi Static Drive

2400

1035

1.39

1070

1.50

1104

1.60

1137

1.70

1168

1.81

2700

1073

1.64

1104

1.76

1136

1.87

1167

1.99

1198

2.11

3000

1117

1.93

1146

2.05

1176

2.17

1205

2.31

1233

2.44

3300

1165

2.30

1194

2.41

1220

2.52

1248

2.66

1275

2.79

3600

1215

2.73

1242

2.86

1269

2.98

1295

3.10

1319

3.22

3 HP Over-Sized Motor & High Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.

Advertising