27

RT-PRC016-EN

Performance
Data

External Static Pressure (Pascals)

275

300

325

350

375

400

425

450

475

500

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

2.24 Nom kW Standard Motor & Drive

5440

917

1.36

945

1.47

973

1.60

999

1.72

1024

1.84

1048

1.97

1072

2.10

1095

2.23

1117

2.37

1140

3.36

6120

951

1.57

979

1.69

1007

1.82

1033

1.94

1059

2.07

1082

2.20

1107

2.34

1130

2.49

1152

2.63

1173

3.71

6800

988

1.82

1015

1.95

1042

2.08

1068

2.21

1093

2.35

1117

2.48

1142

2.63

1164

2.76

1187

2.91

1209

4.11

7480

1028

2.09

1053

2.23

1078

2.38

1103

2.52

1128

2.66

1152

2.81

1176

2.95

1198

3.10

1221

3.25

-

-

8160

1071

2.41

1095

2.55

1119

2.70

1142

2.86

1166

3.02

1189

3.17

1212

3.33

-

-

-

-

-

-

2.24 Nom kW Standard Motor & High Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Table PD-14 — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (SI)

External Static Pressure (Pascals)

25

50

75

100

125

150

175

200

225

250

m

3

/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

2.24 Nom kW Standard Motor & Low Static Drive

2.24 Nom kW Standard Motor & Drive

5440

-

-

-

-

-

-

-

-

718

0.72

754

0.82

789

0.93

822

1.03

856

1.14

887

1.25

6120

-

-

-

-

-

-

731

0.81

764

0.90

797

0.99

829

1.10

860

1.22

892

1.34

922

1.46

6800

-

-

715

0.81

747

0.90

782

1.01

814

1.11

844

1.21

874

1.32

903

1.44

932

1.56

960

1.69

7480

741

0.95

773

1.04

803

1.14

834

1.24

864

1.36

894

1.48

922

1.59

948

1.70

975

1.82

1001

1.95

8160

803

1.21

833

1.31

861

1.42

887

1.52

916

1.64

945

1.77

972

1.90

997

2.02

1022

2.14

1046

2.27

Table PD-14a — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (IP)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3 HP Standard Motor & Low Static Drive

3 HP Standard Motor & Drive

3200

-

-

-

-

-

-

-

-

718

0.97

754

1.10

789

1.25

822

1.38

856

1.53

887

1.67

3600

-

-

-

-

-

-

731

1.08

764

1.20

797

1.33

829

1.48

860

1.63

892

1.79

922

1.95

4000

-

-

715

1.09

747

1.21

782

1.35

814

1.49

844

1.63

874

1.77

903

1.93

932

2.09

960

2.27

4400

741

1.27

773

1.40

803

1.53

834

1.67

864

1.82

894

1.98

922

2.13

948

2.28

975

2.44

1001

2.62

4800

803

1.62

833

1.76

861

1.90

887

2.04

916

2.20

945

2.38

972

2.55

997

2.71

1022

2.87

1046

3.04

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3 HP Standard Motor & Drive

3200

917

1.82

945

1.97

973

2.14

999

2.30

1024

2.47

1048

2.65

1072

2.82

1095

3.00

1117

3.17

1140

3.36

3600

951

2.11

979

2.27

1007

2.43

1033

2.60

1059

2.78

1082

2.95

1107

3.14

1130

3.33

1152

3.52

1173

3.71

4000

988

2.44

1015

2.62

1042

2.79

1068

2.97

1093

3.15

1117

3.33

1142

3.52

1164

3.70

1187

3.91

1209

4.11

4400

1028

2.81

1053

3.00

1078

3.19

1103

3.38

1128

3.57

1152

3.77

1176

3.96

1198

4.15

1221

4.36

-

-

4800

1071

3.23

1095

3.42

1119

3.62

1142

3.83

1166

4.04

1189

4.25

1212

4.46

-

-

-

-

-

-

3 HP Standard Motor & High Static Drive

Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.

Advertising