Performance data – Trane TSC060-120 User Manual

Page 32

Advertising
background image

32

RT-PRC016-EN

Performance
Data

Table PD-24 — Air Temperature Rise Across Electric Heaters (Degrees C)

kW

3400 m

3

/h

4100 m

3

/h

5100 m

3

/h

5800 m

3

/h

6800 m

3

/h

380V / 415V

Voltage

Stages

TSC060AD

TSC072AD

TSC090AD

TSC102AD

TSC120AD

07.5 / 09.0

380-415/50/3

2

6.6 / 7.9

—-

—-

—-

—-

10.9 / 13.0

380-415/50/3

2

9.6 / 11.4

—-

—-

—-

—-

11.3 / 13.5

380-415/50/3

1

—-

8.3 / 9.9

6.6 / 7.9

—-

—-

14.4 / 17.2

380-415/50/3

2

12.6 / 15.1

—-

—-

—-

—-

16.9 / 20.2

380-415/50/3

2

—-

12.4 / 14.8

9.9 / 11.8

8.7 / 10.4

7.4 / 8.9

22.6 / 26.9

380-415/50/3

2

—-

16.5 / 19.7

13.2 / 15.7

11.7 / 13.9

9.9 / 11.8

33.8 / 40.4

380-415/50/3

2

—-

—-

—-

—-

14.8 / 17.7

Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (C

0

) across Elect Htr = (kW x 2985)/( m

3

/h)

Table PD-24A — Air Temperature Rise Across Electric Heaters (Degrees F)

kW

2000 CFM

2400 CFM

3000 CFM

3400 CFM

4000 CFM

380V / 415V

Voltage

Stages

TSC060AD

TSC072AD

TSC090AD

TSC102AD

TSC120AD

07.5 / 09.0

380-415/50/3

2

11.9 / 14.2

—-

—-

—-

—-

10.9 / 13.0

380-415/50/3

2

17.2 / 20.5

—-

—-

—-

—-

11.3 / 13.5

380-415/50/3

1

—-

14.9 / 17.8

11.9 / 14.2

—-

—-

14.4 / 17.2

380-415/50/3

2

22.8 / 27.2

—-

—-

—-

—-

16.9 / 20.2

380-415/50/3

2

—-

22.3 / 26.6

17.8 / 21.3

15.7 / 18.8

13.4 / 16.0

22.6 / 26.9

380-415/50/3

2

—-

29.8 / 35.4

23.8 / 28.3

21.0 / 25.0

17.9 / 21.3

33.8 / 40.4

380-415/50/3

2

—-

—-

—-

—-

26.7 / 31.9

Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (F

0

) across Elect Htr = (kW x 3414)/(1.08 x CFM)