Battery Configurations

975-0012-01-02 Rev A

B–11

Connect to inverter

To connect to the inverter:
1. Connect a cable from the positive terminal of the first battery string to the

inverter’s positive DC terminal (via a fused device).

2. Connect the negative terminal of the last battery string to the negative

terminal of inverter’s DC terminal.

Figure B-6 Battery Wiring 24-volt - Parallel Configuration - Step 3

Important:

Connecting the positive and negative wires to the inverter from different

strings ensures a balanced charge/discharge through the batteries, resulting in longer run
times and improved battery life.

+

6 V

6 V

+

+

6 V

6 V

+

6 V

6 V

6 V

6 V

+

24 V INVERTER

(Total battery capacity = 200 Ah)

+

+

+

+

Connection from Series String 2 to

inverter's negative (–) terminal

Series String 2

Series String 1

Connection from Series String 1
to inverter's positive (+) terminal

Each battery's amp-hour

rating is 100 Ah.

SHUNT

DC Disconnect (can be

either a circuit breaker or a

fuse with a disconnect)