Table 3-1 Battery Type Selector Switch Settings

Switch
Position

Description

12-volt Models

24-volt Models

Charge Function

Float
Voltage

Bulk/
Equalize*
Voltage

Float
Voltage

Bulk/
Equalize*
Voltage

Equalize Charge
Rate

Equalize Time

0

Equalize 1 -
equalizes at a rate
equal to the
battery bank
capacity (in amp-
hours) divided by
40.

13.2

*15.0

26.4

*30.0

Battery Capacity
Setting (C/40)

6 hrs. minimum
12 hrs. maximum

1

Equalize 2 -
charges at a rate
set by the
BATTERY
CHARGER
RATE control.

13.2

*15.5

26.4

*31.0

Battery Charger
Rate Setting
(manual)

6 hrs. minimum
12 hrs. maximum

2

Deep Cell Lead
Acid 2

13.3

15.0

26.6

30.0

Provides an additional Float and Bulk
settings for deep cycle, lead acid batteries.
Refer to the battery manufacturer’s
recommendation for Float and Bulk
settings.

3

Not Specified

13.6

14.3

27.2

28.6

Provides an additional setting of Bulk and
Float voltages.

4

Gel Cel 2

13.7

14.4

27.4

28.8

Recommended for gel cell batteries that
specify high float voltages. Check with the
battery’s manufacturer.

5

Gel Cell 1

13.5

14.1

27.0

28.2

Typical gel cell setting.

6

PcCa-lead
Calcium

13.2

14.3

26.4

28.6

Use this setting for sealed type car
batteries.

7

Deep Cycle
Lead Acid 1
(Default Setting)

13.4

14.6

26.6

29.2

Factory setting for typical deep cycle
lead acid batteries.

8

NiCad 1

14.0

16.0

28.0

32.0

Use for NiCad battery systems.

9

NiCad 2

14.5

16.0

29.0

32.0

Recommended for use with nickel iron
batteries.

Advertising