Multi-wire Branch Circuits

975-0012-01-02 Rev A

C–3

Figure C-2 Multi-wire Branch Circuit Wiring and Current Flow

Figure C-3 120 Vac Inverter Incorrectly Wired in a Multi-wire Branch Circuit

Load Center

L1

L2

Neutral

Ground

120 Vac

120 Vac

15 A

Breaker

(Ganged)

240 Vac

from Grid

Bare - Ground

Single White - Neutral
(Current Flow 0 A)

Black - Hot
(Current Flow 15 A)

Red - Hot
(Current Flow 15 A)

Bare - Ground Splice

White - Neutral Splice
(Current Flow 15 A)

Out-of-Phase current
subtract at this point
(Current Flow 0 A)

15 A

Breaker

(Ganged)

Load Center

L1

L2

Neutral

Ground

120 Vac

120 Vac

15 A

Breaker

(Ganged)

240 Vac

from Grid

Bare - Ground

Single White - Neutral
(Current Flow 10 A)

Black - Hot
(Current Flow 5 A)

Red - Hot
(Current Flow 15 A)

White - Neutral Splice
(Current Flow 15 A)

When unbalanced
current flows through
each leg, only the
difference current
flows through the
neutral return wire.

15 A

Breaker

(Ganged)

Load Center

L1

L2

Neutral

Ground

120 Vac

120 Vac

15 A

Breaker

(Ganged)

Bare - Ground

Single White - Neutral
(Current Flow 30 A)

Black - Hot
(Current Flow 15 A)

Red - Hot
(Current Flow 15 A

White - Neutral Splice
(Current Flow 15 A)

WARNING: FIRE HAZARD
The in-phase currents ADDS
at this point exceeding wire
capacity!

15 A

Breaker

(Ganged)

120 Vac

Inverter or Generator