DC Wiring

975-0012-01-02 Rev A

2–13

DC Wiring

This section describes the DC wiring requirements and how to make the
connections. It provides the required cable and wire sizes, recommended lengths
for cables, and disconnect/circuit breaker requirements.

DC Circuit Grounding

Grounding is an important part of the system installation and must be performed
correctly to ensure safe operation of the equipment. Grounding requirements vary
by country and application. Consult the NEC for specific requirements.
The ground conductor should be sized appropriately for the over-current
protection device being used and according to NEC 250-95 (Ninth Edition)
(see Table 2-2 below for a portion of the NEC code).

General DC Grounding Requirements

This product is intended to be installed as part of a permanently grounded
electrical system per the National Electric Code ANSI/NFPA 70 (current edition).
This is the single point earth ground for the inverter system.
To ground the DC circuits:
1. Connect the negative (-) terminal of the battery bank to an appropriately sized

conductor and connect it to the ground bus in the DC Disconnect.

2. Connect an appropriately sized conductor to the Ground bus in the DC

Disconnect and connect it to the primary system ground.

The system ground is the same ground used by the AC side of the system.

Table 2-2 Safety Ground Conductor Size

Size of Over-current Device
Protecting the Conductor

Minimum Size of the Copper
Ground Wire

30 or 60 amp

#10 AWG

100 amp

#8 AWG

200 amp

#6 AWG

300 amp

#4 AWG

400 amp

#3 AWG