AC Wiring

975-0012-01-02 Rev A

2–23

Before wiring the input of the inverter, refer to Table 2-5 below for the minimum
recommended wire size.

Important:

The lower AC cover varies depending on the model. DR24XX and

DR36XX models are equipped with a conduit box and not a plate. The conduit box is
required for the larger diameter wire providing ample bending radius.

Figure 2-15 AC Side Cover Panels

Screws

Standard Cover Plate

High Power Conduit Box

DR15XX

DR24XX and DR36XX models

Important:

Refer to the NEC for actual wire sizes for specific installations.

Table 2-5 Minimum Recommended Wire Size, Torque Values (Input and Output), and Maximum Output
Breaker Size

Inverter
Model

AC Input

AC Output

Torque Value
for Terminal
Connections

Maximum
Output
Breaker Size

120 Vac

220-240 Vac

120 Vac

220-240 Vac

DR1512

#8 or 6 AWG

#10 AWG

#10 AWG

#16 AWG

16 in-lbs
(1.8 nm)

30 amps AC

DR2412

#6 AWG

#10 AWG

#10 AWG

#14 AWG

16 in-lbs
(1.8 nm)

30 amps AC

DR1524

#8 or 6 AWG

#10 AWG

#10 AWG

#16 AWG

16 in-lbs
(1.8 nm)

30 amps AC

DR2424

#6 AWG

#10 AWG

#10 AWG

#14 AWG

16 in-lbs
(1.8 nm)

30 amps AC

DR3624

#6 AWG

Not Available

#8 AWG

Not Available

16 in-lbs
(1.8 nm)

30 amps AC

WARNING: Fire Hazard

To reduce the risk of fire, connect only to a circuit provided with the maximum
branch-circuit overcurrent protection noted above in accordance with the National
Electrical Code, ANSI/FFPA70.