Operation

3–8

975-0012-01-02 Rev A

Use

Table 3-2 to find the approximate setting of the Battery Charge Rate

potentiometer. The settings do not need to be exact, but should be as close as
possible to the actual value required.

Over Discharge Protection/AC Transfer Voltage

The Over Discharge Protection/AC Transfer Voltage potentiometer performs two
related functions. When set between the 2 and 5 o’clock position (right), both
ODP and the AC Transfer Voltage function simultaneously (see table on next
page). When the potentiometer is set between the 9 and 1 o’clock position (left),
only the AC Transfer Voltage is functional (ODP is disabled).

Important:

The potentiometer does not have an arrow to indicate its position. Use a

small blade screwdriver and rotate the control completely CCW to find the start position.
Rotate the potentiometer CW to the desired position (i.e., halfway between the stops for a
50% setting).

Table 3-2 Approximate Charge rate Setting/Amperage

Model

Percent of Potentiometer Rotation (between stops)

0% Min.

25%

50%

75%

100%

Max

DR1512
DR2424
DR3624

0 amps

17.5 amps

35 amps

52.5 amps

70 amps

DR2412

0 amps

30 amps

60 amps

90 amps

120 amps

DR1524

0 amps

8.75 amps

17.5 amps

26.25 amps 35 amps

Figure 3-4 Battery Charger Rate Potentiometer (DR1512 values used)

0%

(0 amps

100%

(70 amps)

Example 1

50%

(35 amps

75%

(50 amps)

Example 2

25%

(17.5 amps

Important:

The ODP is not scaled. It is either on or off. The min/max settings only

refer the AC transfer function.