Table a.3 – Xantrex Technology XPR 150-40 User Manual

Page 70

Advertising
background image

Specifications and Characteristics
Electrical Specifications—Summary

68

Operating Manual for XPR Series Power Supply

Table A.3Specifications for 6000 Watt units (80V to 600V Models)

Models

80–75

100–60

150–40

300–20

600–10

Output Ratings:

Output Voltage

1

Output Current

2

Output Power

1. Minimum output voltage is <0.3% of rated voltage at zero output setting.
2. Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.

0–80 V
0–75 A
6000 W

0–100 V
0–60 A
6000 W

0–150 V
0–40 A
6000 W

0–300 V
0–20 A
6000 W

0–600 V
0–10 A
6000 W

Line Regulation:

3

Voltage

(0.01% of Vmax)

Current (0.05% of Imax)

3. For input voltage variation over the AC input voltage range, with constant rated load.

8 mV
37.5 mA

10 mV
30 mA

15 mV
20 mA

30 mV
10 mA

60 mV
5 mA

Load Regulation:

4

Voltage (0.05% of Vmax + 5 mV)
Current (0.1% of Imax + 20 mA)

4. For 0–100% load variation, with constant nominal line voltage.

45 mV
95 mA

55 mV
80 mA

80 mV
60 mA

155 mV
40 mA

305 mV
30 mA

Meter Accuracy:

Voltage (0.5% of Vmax + 1 count)
Current (0.5% of Imax + 1 count)

0.5 V
0.48 A

0.6 V
0.4 A

1.75 V
0.3 A

2.5 V
0.2 A

4.0 V
0.06 A

Output Noise (0–20 MHz):

Voltage (p–p)

100 mV

100 mV

150 mV

250 mV

350 mV

Output Ripple (rms):

Voltage
Current

5

5. Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.

15 mV
320 mA

20 mV
230 mA

20 mV
120 mA

30 mV
50 mA

80 mV
25 mA

OVP Adjustment Range:

(0% to 103% of Vmax)

0–88 V

0–110 V

0–165 V

0–330 V

0–660 V

Efficiency:

6

6. Typical efficiency at nominal input voltage and full output power.

0.89

0.90

0.90

0.91

0.91

Advertising