Installation errors in standpipe – VEGA VEGAPULS 56K User Manual

Page 17

Advertising
background image

VEGAPULS 56K

17

22915-EN-041227

Pipe antenna: The surge pipe open to the bottom
must have a ventilation or compensation hole on top

The polarisation direction is in the same plane as the
marking hole. The sensor must be aligned with the
marking hole to the rows of holes or the openings.

Correct

Incorrect

Installation errors in standpipe

Missing ventilation hole

Pipe antenna systems must be provided with
a vent hole at the upper end of the surge
pipe. A missing hole causes wrong measure-
ments.

Wrong polarisation direction

When measuring in a surge pipe, especially
when there are holes for mixing, it is impor-
tant that the radar sensor is aligned with the
rows of holes. The rows of holes of the surge
pipe (displaced by 180°) must be in one
plane with the polarisation direction of the
radar signals. The polarisation direction is the
same plane as the marking hole.

Marking
hole

DN 50

ø50

Mounting and installation

Lockable measuring pipe on a pipe antenna system

Ball valve

Standpipe ventilation

Deflector