36

VEGAPULS 56K

22915-EN-041227

Error codes:

E013

No valid measured value
- Sensor in the warm-up phase
- Loss of the useful echo

E017

Adjustment span too small

E036

Sensor program not operating
- Sensor must be reprogrammed

(service)

- Fault signal also appears during

programming

E040

Hardware failure, electronics
defective

Adjustment steps

On the following pages you will find the com-
plete menu schematic of the adjustment mod-
ule MINICOM.
Set up the sensor in the numbered se-
quence:
1. Measuring tube adjustments (only for

measurement in a standpipe)

2. Operating range
3. Adjustment
4. Conditioning
5. Meas. conditions
6. False echo storage (only required when

errors occur during operation).

7. Indication of the useful and noise level
8. Outputs
Short explanations to the setup steps 1 … 8
follow.

1. Measurement in a standpipe

Adjustment is only necessary if the sensor is
mounted in a standpipe (surge or bypass
tube). When measuring in a standpipe, do a
sounding of the distance and correct the
measured value display (which can differ
several percent from the sounded value)
according to the sounding. From then on, the
sensor corrects running time shift of the ra-
dar signal and displays the correct value of
the level in the standpipe (measuring tube).

-

+

ESC

OK

2

4

Tank 1
m (d)
12.345

-

+

ESC

OK

Tank 1
m (d)
12.345

4 ... 20 mA

5.3 Adjustment with adjustment

module MINICOM

You can set up and operate the sensor with
the small, detachable adjustment module
MINICOM just as well as with the PC. The
adjustment module is simply plugged into the
sensor or into the external indicating instru-
ment (optional).

The adjustment module, like the adjustment
program VVO on the PC, provides adjust-
ment options for all sensor versions. There
are some differences with MINICOM, how-
ever. For one thing, it is not possible to enter
your own linearisation curve.

You carry out all adjustment steps with the 6
keys of the adjustment module. A small dis-
play shows you, apart from the measured
value, a short message on the menu item or
the value entered in a menu item.

The volume of information of the small display
cannot be compared with that of the adjust-
ment program VVO, but you will quickly find
your way and carry out your adjustments
quickly and efficiently with the small
MINICOM.

Set-up