Set-up

Connection to a VEGA signal conditioning
instrument

If you operate a HART

®

compatible sensor on

a VEGA signal conditioning instrument, you
have to connect the sensor via a resistor
(see following table) during HART

®

adjust-

ment. This resistor, together with the internal
resistance of the instruments, provides the
value of 250 Ohm required for the HART

®

instrument.

VEGA signal conditioning instr.

Rx

VEGAMET 513, 514, 515, 602
VEGATRENN 544
VEGATOR 521…527

50 … 100 Ohm

VEGAMET 614

no additional

VEGADIS 371

resistor
required

VEGAMET 601

200 … 250 Ohm

VEGASEL 643

150 … 200 Ohm

VEGAMET 513 S4, 514 S4
515 S4,
VEGALOG EA card

100 … 150 Ohm