Electrical connection

Measuring system with VEGAPULS 56K Ex, 56K Ex0 via a safety barrier in
Ex area on active PLC

• Two-wire technology (loop powered), power supply via the signal line of the PLC; output

signal 4 … 20 mA (passive).

• Separator transfers the non intrinsically safe PLC circuit to the intrinsically safe circuit, so

that the sensor can be used in Ex zone 1 (VEGAPULS 56K Ex) or in zone 0 (VEGAPULS
56K Ex0)

• max. resistance of the signal cable 15

Ω per wire

• Optional external indicating instrument with analogue and digital display (can be mounted

up to 25 m away from the sensor).

• Adjustment with PC, HART

®

handheld or adjustment module MINICOM (can be plugged into

the sensor or into the external indicating instrument VEGADIS 50).

HART

®

handheld

Ex area

Non Ex area

Safety barrier
(see „3.3 Approvals“)

VEGA-
CONNECT 2

VEGADIS 50 Ex

passive

1 )

PLC

EEx ia

1)

4 … 20 mA passive means that
the sensor or the PLC consumes a
level-dependent current of
4 … 20 mA. The PLC reacts
electrically like a varying resistor
(consumer) to the PLC.