VEGA Modbus-TCP, ASCII protocol User Manual

Page 15

Advertising
background image

15

2 ASCII protocol

Modbus-TCP, ASCII protocol • VEGAMET 391/624/625, VEGASCAN 693, PLICSRADIO C62

30768-EN-130701

Answer:

=001# 067.3%

=002# 824.6%

=003#-067.3%

% Block enquiry with range

As answer to the range enquiry, the range stated in the enquiry with

PC/DCS values is delivered. The measured value is transmitted with

three decimal places in front of the decimal point and one decimal

place after the decimal point without unit.

Number of bytes

Character

Identifier

1

%

Begin

1 … 3

001 … 030 or 1 … 30

Separator

1

-

End

1 … 3

001 … 030 or 1 … 30

End identification

1

CR

Identifier: "%" (1 character)

Start: Start no. of the requested PC/DCS output (1 … 3 charac-

ters)

Separator: "-" (1 sign)

End: End no. of the requested PC/DCS output (1 … 3 characters)

End identification: Carriage Return CR (1 sign)

Total length of the telegram: 5 … 9 characters

(End-Start+1)-times repetition of the following telegram

Number of bytes

Character

T1

1

=

DCS no.

3

001 … 030

T2

1

#

Value

5 … 6

-067.3

T3

1

%

End identification

1

CR

T1: "=" (1 character)

DCS no.: No. of the PC/DCS output as 3-digit decimal number

T2: "#" (1 character)

Value: Numerical value of the PC/DCS output or with interferred

measured value the text "FAULT"

Formatting of the value:

Character

Meaning

1

"- ": Minus with negative numbers
" ": Space with positive numbers

2 … 4

3-digit number

Enquiry of the control

system

Reply from the signal

conditioning instrument

Advertising